| Notes |
| Date |
Text |
| 2015-10-22 06:57:04 | 1ST REVIEW: FBC 2010 MECHANICAL | | | REVISION # 15100297 | | | MASTER # 15010300 | | | 10/22/15 | | | | | | 1) THE WPB DEVELOPMENT SERVICES BUILDING DIVISION | | | REQUIRES SEPARATE PERMITS FOR KITCHEN HOODS AND FIRE | | | SUPRESSION SYSTEMS. PLEASE REMOVE SHEET M7.1 & M7.2 | | | FROM THE REVISED PLAN SETS OR PLACE NOTES ON THE PLAN | | | TO CLARIFY THAT THE GREASE DUCT SHOWN IN THE TENANT | | | SPACE IS FOR REFERENCE ONLY, AND WILL BE INSTALLED | | | UNDER A SEPARATE PERMIT. | | | 2) SHEET M2.2: PROVIDE ENGINEERED TIE-DOWN DETAILS FOR | | | THE NEW CU 1-9 AND AC STAND- SECTION 301.12 FBC-10 | | | MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|