| 2015-11-04 17:44:58 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION |
| | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010 |
| | EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS |
| | APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED. |
| | |
| | 1. FIRE ALARM WORK SHALL BE UNDER A SEPARATE STAND |
| | ALONE PERMIT. |
| | 2. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN |
| | OUTLET AT EVERY PEDESTRIAN ENTRY TO EVERY COMMERCIAL |
| | SPACE. PROVIDE SIGN JUNCTION OUTLET ABOVE EACH ENTRY |
| | DOOR. |
| | 3. NEC 210.8(B) REQUIRES THAT EVERY OUTLET IN A KITCHEN |
| | BE GFI PROTECTED. THIS INCLUDES THE OPEN KITCHEN AREAS |
| | DESCRIBED ON THE PLANS. |
| | 4. FBC-ENERGY SECTION C402.4.8 REQUIRES THAT ALL |
| | RECESSED LIGHTING IN THE BLDG. THERMAL ENVELOPE BE IC |
| | PROTECTED AND SEALED TO LIMIT AIR LEAKAGE BETWEEN THE |
| | CONDITIONED AND NON-CONDITIONED SPACES. |
| | 5. FBC-B SECTION 1011, THE PATH OF EGRESS TRAVEL TO THE |
| | EXITS SHALL BE MARKED. A SIGN IS REQUIRED TO INDICATE |
| | THE CORRIDOR VIA THE VESTIBULE. |
| | 6. NEC 408.4(B) REQUIRES THAT THE LOCATION OF THE POWER |
| | SOURCE BE MARKED ON ALL SWITCHBOARDS AND PANELBOARDS. |
| | 7. NEC 110.16 REQUIRES THAT ALL ELECTRICAL EQUIPMENT BE |
| | LABELED WITH THE STANDARD ARC-FLASH HAZARD WARNING |
| | LABEL. |
| | 8. FBC-E SECTION C405.5.2, PROVIDE A LIGHTING POWER |
| | ALLOWANCE CHART TO SHOW LIGHTING COMPLIANCE WITH CODE |
| | REQUIREMENTS. |
| | 9. IF PANEL LA HAS A 200 AMP MAIN CIRCUIT BREAKER, WHAT |
| | IS THE 200 AMP DISCONNECT REFLECTED ON THE RISER |
| | DIAGRAM? |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |