Plan Review Notes
Plan Review Notes For Permit 15100271
Permit Number 15100271
Review Stop E
Sequence Number 1
Notes
Date Text
2015-10-29 12:49:23ELECTRICAL PROVISO FOR PERMIT 15020017
 1. NEC 314.27(A)(2) CEILING LUMINAIRE OUTLETS SHALL BE
 LISTED TO SUPPORT A M?NIMUM 50#.
 2. NEC 314.27(C) PADDLE FAN OUTLET BOXES SHALL BE
 LISTED FOR THE PURPOSE.
 3. NEC 410.24 FLOURESCENT FIXTURES MOUNTED ON SUSPENDED
 CEILINGS SHALL BE SECURED BY SCREWS TO CEILING MEMBERS
 ON ALL FOUR CORNERS.
 4. FBC-E SEC. C402.4.8 RECESSED FIXTURES INSTALLED IN
 THE BUILDING THERMAL ENVELOPE SHALL BE SEALED TO LIMIT
 AIR LEAKAGE BETWEEN CONDITIONED & UN-CONDITIONED SPACE.
  