| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | 1- PLEASE PROVIDE A MORE DETAILED RISER DIAGRAM TO |
| | INCLUDE LOAD CALCULATION, PANEL SCHEDULES, GROUNDING |
| | SPECS, WIRE AND CONDUIT ROUTING. FBC-107.3.5.3 AND NEC |
| | 215.5 |
| | 2- PROVIDE CLARIFICATION OF 2 SERVICES IN ONE BUILDING |
| | AND NO OUTSIDE DISCONNECTING MEANS FOR FEEDER |
| | CONDUCTORS ? ARE THESE SERVICE CONDUCTORS CONSIDERED TO |
| | BE OUTSIDE OF THE BUILDING ? NEC 230.2 , NEC 230.6, NEC |
| | 230.70 A1 |
| | 3- EMERGENCY AND EXIT LIGHTS SHALL BE FED BY LIGHTING |
| | CIRCUIT OF SAME LOCAL AREA AHEAD OF ANY LOCAL SWITCHES. |
| | NEC 700.12 F |
| | 4- THE LOCATION OF SMOKE DETECTORS SHALL BE BASED ON |
| | POTENTIAL AMBIENT SOURCES OF SMOKE, MOISTURE, DUST OR |
| | FUMES, AND ELECTRICAL OR MECHANICAL INFLUENCES TO |
| | MINIMIZE NUISANCE ALARMS. (NOT PERMITTED IN BATHROOMS) |
| | NFPA 17.7.1.9 |
| | 5- MANDATORY LIGHTING CONTROLS SHALL BE INSTALLED IN |
| | ALL BATHROOMS (OCCUPANCY SENSORS) FBC-E C405 2.2.2 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |