| Plan Review Notes For Permit 15100233 |
| Permit Number |
15100233 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-12-26 02:50:02 | 1) A SANITARY AND WATER RISER IS REQUIRED FOR THE NEW | | | SERVICE SINK, THE NEW DRINKING FOUNTAINS AND A WATER | | | RISER IS REQUIRED FOR THE ADDITION OF THE NEW TANKLESS | | | WATER HEATER PER THE CITY OF WPB AMEND. TO THE FBC SEC. | | | 107.3.5.1.3. SUBMIT TWO COPIES OF A WATER AND SANITARY | | | RISER FOR REVIEW. 2ND REQUEST. | | | 2) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE | | | GRIPPING SURFACE, NOT TO CENTERLINE AS SHOWN ON | | | SHT.A.03. 2014 FBC ACCESSIBILITY SEC. 609.4. 2ND | | | REQUEST. | | | 3) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 | | | INCHES FROM THE FRONT OF THE WATER CLOSET TO THE | | | CENTERLINE OF THE DISPENSER. 2014 FBCA- SEC.604.7 | | | 4) PLEASE UPDATE THE MODIFICATION NOTE ON SHT.A.01 TO | | | INCLUDE THE ADDITION OF THE DRINKING FOUNTAINS, THE MOP | | | SINK, THE TANKLESS WATER HEATER AND THE ADDITION OF THE | | | HOT WATER PIPING. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|