Plan Review Notes
Plan Review Notes For Permit 15100233
Permit Number 15100233
Review Stop E
Sequence Number 2
Notes
Date Text
2015-11-13 07:50:341ST REVIEW: FBC 2014 5TH ED./ NEC 2011
 EXISTING BUILDING CHANGE OF OCCUPANCY
  
 THIS IS A QUALITY CHECK OF THE PREVIUOS REVIEW
 PERFORMED BY A CONTRACT EMPLOYEE REVERSING THE RESULT
 OF THAT REVIEW TO A STATUS OF FAIL AS FOLLOWS:
  
 THE PLANS ARE DEFICIENT AS MINIMUM PLAN REVIEW CRIRERIA
 TO DETERMINE COMPLIANCE IS NOT PROVIDED. PLEASE INCLUDE
 AN ELECTRCAL TO TO INDICATE AT THE MINIMUM, THE
 FOLLOWING.
  
 FBC 107.3.5.1.2 ELECTRICAL
 1. ELECTRICAL:
 WIRING
 SERVICES
 FEEDERS AND BRANCH CIRCUITS
 OVERCURRENT PROTECTION
 GROUNDING
 WIRING METHODS AND MATERIALS
 GFCIS
 2. EQUIPMENT
 3. SPECIAL OCCUPANCIES
 4. EMERGENCY SYSTEMS
 5. COMMUNICATION SYSTEMS
 6. LOW VOLTAGE
 7. LOAD CALCULATIONS
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  