| 2015-10-13 06:59:19 | 1ST REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1.SHOW CLEAR FLOOR SPACE FOR LAVATORY IN ACCESSIBLE |
| | BATHROOM. |
| | PER WPB AMEN. SEC 107.2.1 |
| | 2.GRAB BARS SHALL COMPLY WITH.FBC ACC SEC 609.4 |
| | POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR |
| | CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM) |
| | MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE |
| | HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A |
| | BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1. |
| | 3.TOILET SHALL COMPLY WITH FBC ACC.SEC 604.2 LOCATION. |
| | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION, |
| | 4. A DRINKING FOUNTAIN IS REQUIRED TO COMPLY WITH FBC |
| | ACC. SEC |
| | 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| | FOUNTAINS. |
| | |
| | 5.PROVIDE SANITARY AND WATER RISER DIAGRAM. |
| | PER WPB AMEN. 107 .3.5.1.3(13) |
| | THE FOLLOWING IS AN UPDATED PLUMBING REVIEW AS OF |
| | 12/9/15; |
| | 1) SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR |
| | PLAN THAT CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK |
| | BEING DONE TO THE EXISTING TOILET ROOM. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 2) SINCE THIS IS A CHANGE OF OCCUPANCY, A SERVICE SINK |
| | IS REQUIRED FOR A MERCANTILE OCCUPANCY PER THE 2014 |
| | FBC-PLBG. TABLE 403.1. |
| | 3) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR REVIEW |
| | FOR ALL NEW PLUMBING FIXTURES. WPB AMEND. TO FBC SEC. |
| | 107.3.5.1.3. |
| | 4) THE LAVATORY IN THE ADA TOILET ROMM AND THE MOP SINK |
| | SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER PER 2014 |
| | FBC -PLBG.SEC.607.1. |
| | 5)SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET AND THE LAVATORY IN ADA TOILET ROOM PER THE 2014 |
| | FBC-ACCESS.SEC.604.3.1. & SEC. 606.2 & SEC.305. |
| | 6) SHT. A.01 - THE UPDATE MODIFICATION NOTE SHALL |
| | INCLUDE THE ADDITION OF THE DRINKING FOUNTAINS, THE MOP |
| | SINK AND THE REQUIREMENT FOR HOT WATER TO THE SCOPE OF |
| | WORK. WPB AMEND.TO FBC 107.2.1 |
| | 7) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 |
| | INCHES TO THE CENTERLINE FROM THE FRONT OF THE WATER |
| | CLOSET. 2014 FBC-ACCESS SEC.604.7. |
| | 8) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014 |
| | FBC-ACCESS. SEC. 307.2. FOR PROTRUSION LIMITS. A SKIRT |
| | ON THE DRINKING FOUNTAINS MAY BE REQUIRED TO COMPLY. |
| | SUBMIT MANUF. SPCIFICATION SHEETS FOR THE ACCESSIBLE |
| | DRINKING FOUNTAIN THAT CLEARLY SHOWS THE HEIGHT OF THE |
| | LEADING EDGES OF THE UNIT. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 9) TWO SETS OF PLANS REQUIRED WPB AMEND. TO FBC |
| | SEC107.1 THREE SETS OF PLANS HAVE BEEN VOIDED AND ONE |
| | HAS NOT LEAVING OMLY ONE SET FOR REVIEW. |