| Plan Review Notes For Permit 15100183 |
| Permit Number |
15100183 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-16 16:26:51 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | PLEASE PROVIDE THE PRODUCT INFORMATION ON THE CORK | | | PRODUCT TO DEMONSTRATE COMPLIANCE WITH THE FOLLOWING | | | SECTIONS: | | | | | | FBC 603.1 FLAME SPREAD | | | | | | FBC 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | PLEASE NOTE THAT THE PERMIT WAS ISSUED WITH PROVISO'S | | | FOR THE ELECTRICAL AND MECHANICAL DESIGN TO BE AMENDED, | | | SEE SHEET A-1.0. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|