| Plan Review Notes For Permit 15100182 |
| Permit Number |
15100182 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-08 12:35:02 | 1ST REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15100182 | | | MASTER #15040093 | | | 10/8/15 | | | | | | 1) SHOW THE REQUIRED CLEARANCE DISTANCE MEASUREMENTS | | | FOR THE AIR HANDLER IN THE CLOSET IN COMPLIANCE WITH | | | SECTION M1305.1.1 FBC-10 RESIDIENTIAL- MINIMUM 4" ALONG | | | THE SIDES, BACK. AND TOP WITH A TOTAL WIDTH OF THE | | | ENCLOSING SPACE BEING AT LEAST 12 INCHES WIDER THAN THE | | | AIR HANDLER. | | | 2) PROVIDE DETAILS AND SHOW THE EXHAUST DUCT RUNS FOR | | | THE DRYER AND BATH FANS: INDICATE THE TYPE AND SIZE OF | | | EXHAUST DUCTS, DUCT RUNS AND LENGTHS, AND EXHAUST | | | TERMINATION LOCATIONS- REFER TO SECTION M1502 FOR DRYER | | | EXHAUST REQUIREMENTS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|