2015-10-08 12:35:021ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15100182
 MASTER #15040093
 10/8/15
  
 1) SHOW THE REQUIRED CLEARANCE DISTANCE MEASUREMENTS
 FOR THE AIR HANDLER IN THE CLOSET IN COMPLIANCE WITH
 SECTION M1305.1.1 FBC-10 RESIDIENTIAL- MINIMUM 4" ALONG
 THE SIDES, BACK. AND TOP WITH A TOTAL WIDTH OF THE
 ENCLOSING SPACE BEING AT LEAST 12 INCHES WIDER THAN THE
 AIR HANDLER.
 2) PROVIDE DETAILS AND SHOW THE EXHAUST DUCT RUNS FOR
 THE DRYER AND BATH FANS: INDICATE THE TYPE AND SIZE OF
 EXHAUST DUCTS, DUCT RUNS AND LENGTHS, AND EXHAUST
 TERMINATION LOCATIONS- REFER TO SECTION M1502 FOR DRYER
 EXHAUST REQUIREMENTS.
  