| 2016-02-25 15:07:32 | 3RD REVIEW 2014 5TH FBC ED. NEC 2011/RESIDENTIAL |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6713 |
| | [email protected] |
| | |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | 1 PLEASE CLARIFY THE INTENT OF HOW SE CABLE IS BEING |
| | RAN FOR 2 MAJOR REASONS ONE IS THE TERMINATIONS OF |
| | ALUMINUM CONDUCTORS INTO THE EQUIPMENT LUGS NEC 110.14 |
| | A & THE OTHER IS THE THERMAL INSULATION TEMPERATURE |
| | LIMITATION TO THE 60 DEGREE COLUMN NEC 338. |
| | 2 PROVIDE AN INTERSYSTEM BONDING STRIP NEC 250.94 |
| | 3 PROVIDE SERVICE ENTRANCE CONDUCTORS SIZES TO MEET |
| | LOAD DEMANDS ALSO STATE IF SERVICE EQUIPMENT HAS A MAIN |
| | DISCONNECT. NEC 230, |
| | 4 IN BATHROOMS GFCI MUST BE WITHIN 3 FT OF EACH OUTSIDE |
| | EDGE BASIN. NEC 210.52 D (DOUBLE SINKS REQUIRE EITHER 2 |
| | ON EACH SIDE OR 1 IN THE MIDDLE TO BE COMPLIANT.) |
| | 5 SHOW PANEL LOCATIONS ON ELECTRICAL FLOOR PLAN AS WELL |
| | AS WH & AC DISCONNECTS. WBA 107 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | |