| 2015-12-23 18:58:08 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6700 |
| | [email protected] |
| | ALTERNATE CONTACT |
| | MIKE ALBARRAN |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |
| | PROVIDE 2 SETS OF PLANS AS REQUIRED BY CITY OF WEST |
| | PALM BEACH FBC 107 |
| | PROPERLY LABEL EACH AREA AND PROVIDE SCOPE OF WORK PER |
| | CWPB FBC 107 |
| | SHOW SERVICE LOCATION ON FLOOR PLANS AND SHOW PROPER |
| | GROUNDING AND BONDING ON RISER , NEC 250.53 WATER/METAL |
| | PIPE , NEC 250.94 INTERSYSTEM. |
| | SHOW HOW SE CABLE IS BEING RAN AS YOUR FEEDER |
| | CONDUCTORS NEC 338 |
| | TAMPER RESISTANT RECEPTACLES REQUIRED PER NEC 406.11 |
| | R404.1 LIGHTING EQUIPMENT (MANDATORY). |
| | A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| | EFFICACY LAMPS. |
| | R402.4.4 RECESSED LIGHTING. |
| | RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| | ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED |
| | LUMINAIRES SHALL BE IC-RATED AND LABELED AS HAVING AN |
| | AIR LEAKAGE RATE NOT MORE THAN 2.0 CFM (0.944 L/S) WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E 283 AT A 1.57 PSF (75 |
| | PA) PRESSURE DIFFERENTIAL. ALL RECESSED LUMINAIRES |
| | SHALL BE SEALED WITH A GASKET OR CAULK BETWEEN THE |
| | HOUSING AND THE INTERIOR WALL OR CEILING COVERING. |
| | ALL RECESSED LIGHTING OVER SHOWER OR BATHTUB SHALL BE |
| | VAPOR TIGHT. |