| 2015-11-09 16:30:59 | RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- THERE IS NO COORDINATION WITH EQUIPMENT SIZING |
| | CALCULATIONS AND FLOOR PLAN ON SHEET M1.00 SUBMITTED. |
| | SHEET M1.00 SHOWS ONLY ONE A/C UNIT. EQUIPMENT. ALSO, |
| | EQUIPMENT LISTED ON THE A/C PLAN DOESN'T MATCH |
| | EQUIPMENT SIZING CALCULATIONS. PROVIDE EQUIPMENT SIZING |
| | CALCULATIONS THAT MATCH A/C PLAN. SEC. 107.2.. 1 CITY |
| | AMENDMENTS. |
| | |
| | 2- CONDENSING UNIT MOUNTING DETAIL SHOWN ON SHEET M1.00 |
| | IS INADEQUATE. (4) 2 1/4" TAPCONS ARE NOT ENOUGH |
| | SPECIFICATIONS TO HOLD THE CONDENSING UNIT. PROVIDE A |
| | COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW IS THE |
| | CONDENSING UNIT ATTACHED TO RESIST THE WIND LOADS OF |
| | SEC. R301 OF FBC-RESIDENTIAL. |
| | AND, CLEARLY SPECIFY LOCATION OF ALL CONNECTORS. |
| | |
| | 3- DRAWING M1.00 : PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH THE RETURN AIR |
| | SEC. M1602 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | SPECIFY SIZE OF GRILL SHOWN ON THE FIRST FLOOR AND |
| | SECOND FLOOR AND SPECIFY HOW ARE THE RETURN GRILLS |
| | CONNECTED TO THE AIR HANDLER UNIT. |
| | |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH THE BALANCED RETURN AIR SEC. M1602.4 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014) FOR ALL THE |
| | BEDROOMS ON THE SECOND FLOOR. |
| | |
| | 5- PLANS SUBMITTED ARE NOT ELECTRONICALLY TRANSMITTED |
| | PLANS. ENGINEER NEEDS TO PROVIDE ORIGINAL SEAL AND |
| | SIGNATURE ON ALL PLANS AS REQUIRED BY 61G15-23.002 AND |
| | CHAPTER 471 F.S. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |