| 2015-10-26 19:22:29 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE ???2011 |
| | EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH |
| | EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS |
| | APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED. |
| | 1. GENERAL NOTES #12: DO YOU REALLY WANT TO RUN A #2CU |
| | GROUND CONDUCTOR TO THE 15 -20 AMP 125 VAC OUTLET? |
| | CORRECT YOUR NOTE ACCORDINGLY. |
| | 2. IN YOUR NOTES YOU SEEK TO OBTAIN A 5 OHM READING ON |
| | THE GROUNDING. I BELIEVE THAT SUCH A READING IS |
| | UNOBTAINABLE, ARE YOU SURE YOU DON?T MEAN 25 OHM? |
| | 3. IN ADDITION TO GROUND THE GENERATOR, A FOUNDATION |
| | GROUND TO THE GENERATOR PAD STEEL SHALL BE RUN AS WELL. |
| | PER NEC 250.66. |
| | 4. PROVIDE A FEEDER DIAGRAM AS DIRECTED IN NEC 215.5. |
| | THIS DIAGRAM SHALL INCLUDE LOAD CALCS AND CONDUCTOR |
| | SIZING. |
| | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| | FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED |
| | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |