2015-10-26 19:22:29THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE ???2011
 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
 1. GENERAL NOTES #12: DO YOU REALLY WANT TO RUN A #2CU
 GROUND CONDUCTOR TO THE 15 -20 AMP 125 VAC OUTLET?
 CORRECT YOUR NOTE ACCORDINGLY.
 2. IN YOUR NOTES YOU SEEK TO OBTAIN A 5 OHM READING ON
 THE GROUNDING. I BELIEVE THAT SUCH A READING IS
 UNOBTAINABLE, ARE YOU SURE YOU DON?T MEAN 25 OHM?
 3. IN ADDITION TO GROUND THE GENERATOR, A FOUNDATION
 GROUND TO THE GENERATOR PAD STEEL SHALL BE RUN AS WELL.
 PER NEC 250.66.
 4. PROVIDE A FEEDER DIAGRAM AS DIRECTED IN NEC 215.5.
 THIS DIAGRAM SHALL INCLUDE LOAD CALCS AND CONDUCTOR
 SIZING.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.