| 2015-10-05 11:32:46 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | ELEVATION CERTIFICATE FOR MAIN HOUSE: |
| | |
| | C2E, ELEVATION OF MECHANICAL EQUIPMENT TO BE ABOVE 7.5, |
| | ELEVATION CERTIFICATE STATES ELEVATION IS 6.80. PLEASE |
| | NOTE THAT PHOTOGRAPHS SHOW THE MECHANICAL EQUIPMENT |
| | ELEVATED ON STANDS. PLEASE REVISE ELEVATION TO STATE |
| | ELEVATION OF EQUIPMENT (NOT CONCRETE PAD) AND ALSO |
| | REVISE COMMENTS IN SECTION D. |
| | |
| | SEE INSTRUCTIONS FOR BUILDING PHOTOGRAPHS, PHOTOGRAPHS |
| | MUST SHOW THE FOUNDATION WITH REPRESENTATIVE EXAMPLES |
| | OF FLOOD OPENINGS OR VENTS. |
| | |
| | ELEVATION CERTIFICATE FOR POOL HOUSE: |
| | |
| | A9(D) INDICATES THAT THERE ARE ENGINEERED FLOOD |
| | OPENINGS, PLEASE CLARIFY AS TO LOCATION (IN COMMENTS). |
| | FLOOD VENTS CAN BE USED ONLY FOR STORAGE, PARKING, AND |
| | ACCESS. ONLY THE PORTION OF THE FLOOD VENT WHICH IS |
| | BELOW 7.5' CAN BE COUNTED TOWARDS OPENINGS. COMPLIANCE |
| | NOT CLEAR. |
| | |
| | C2(A) STATES FFE IS 7.4, 7.5 REQUIRED. IF SLAB IS 7.5, |
| | FLOOD VENTS ARE NOT REQUIRED. |
| | |
| | SEE INSTRUCTIONS FOR PHOTOGRAPHS, FLOOD VENTS IN WALLS |
| | TO BE INCLUDED. |
| | |
| | SEE INSTRUCTIONS FOR ELEVATION CERTIFICATE, FLOOD VENT |
| | PRODUCT APPROVAL TO BE ATTACHED TO THE ELEVATION |
| | CERTIFICATE. I HAVE PRINTED THE PRODUCT APPROVAL COVER |
| | SHEET AND ATTACHED THE FLOOD VENT INFORMATION TO THE |
| | ELEVATION CERTIFICATE FOR THE HOUSE. PLEASE PROVIDE |
| | ANOTHER SET FOR THE CABANA, IF APPLICABLE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |