| Plan Review Notes For Permit 15100053 |
| Permit Number |
15100053 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-06 09:40:08 | 1ST REVIEW: FBC 2010 MECHANICAL | | | MASTER #15050527- PUBLIX REFRIGERATION. | | | SUBMITTAL # 15100053- PROVISO RESPONSES. | | | REVIEWED 10/6/15 | | | | | | 1) THE REQUESTED CERTIFICATION OF MECHANICAL CENTER | | | INSPECTION WAS NOT SUBMITTED. | | | 2) IN RESPONSE TO PROVISO #3 A MANUFACTURER'S PRODUCT | | | DATA SHEET FOR THE ENTRY DOOR WAS SUBMITTED. PLEASE | | | REFER TO DEPT OF COMMUNITY AFFAIRS RULE 9N-3 AND | | | PROVIDE THE REQUESTED MIAMI-DADE NOA OR FL. PRODUCT | | | APPROVAL FOR THE DOOR. | | | 3) IN RESPONSE TO PROVISO #4 FOR THE SEQUENCE OF | | | OPERATION FOR REFRIGERANT LEAK DETECTORS ON THE | | | MECHANICAL CENTER, LEAK DETECTOR SPECIFICATIONS WERE | | | SUBMITTED WITH OPERATIONAL PROCEDURES FOR WALK-IN | | | BOXES. PLEASE REFER TO SECTION 1105 FBC-10 MECHANICAL | | | AND ALL SUB-SECTIONS OUTLINING REQUIRED COMPLIANCE FOR | | | LEAK DETECTION AND VENTILATION REQUIREMENTS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|