2015-10-06 09:40:081ST REVIEW: FBC 2010 MECHANICAL
 MASTER #15050527- PUBLIX REFRIGERATION.
 SUBMITTAL # 15100053- PROVISO RESPONSES.
 REVIEWED 10/6/15
  
 1) THE REQUESTED CERTIFICATION OF MECHANICAL CENTER
 INSPECTION WAS NOT SUBMITTED.
 2) IN RESPONSE TO PROVISO #3 A MANUFACTURER'S PRODUCT
 DATA SHEET FOR THE ENTRY DOOR WAS SUBMITTED. PLEASE
 REFER TO DEPT OF COMMUNITY AFFAIRS RULE 9N-3 AND
 PROVIDE THE REQUESTED MIAMI-DADE NOA OR FL. PRODUCT
 APPROVAL FOR THE DOOR.
 3) IN RESPONSE TO PROVISO #4 FOR THE SEQUENCE OF
 OPERATION FOR REFRIGERANT LEAK DETECTORS ON THE
 MECHANICAL CENTER, LEAK DETECTOR SPECIFICATIONS WERE
 SUBMITTED WITH OPERATIONAL PROCEDURES FOR WALK-IN
 BOXES. PLEASE REFER TO SECTION 1105 FBC-10 MECHANICAL
 AND ALL SUB-SECTIONS OUTLINING REQUIRED COMPLIANCE FOR
 LEAK DETECTION AND VENTILATION REQUIREMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719