Plan Review Notes
Plan Review Notes For Permit 15100053
Permit Number 15100053
Review Stop B
Sequence Number 1
Notes
Date Text
2015-10-07 13:59:45BUILDING PLAN REVIEW
 W. P. B. REVISION: 15100053
 W. P. B. PERMIT: 15050527 UNDER THE 2010 FBC
 ADD: 831 VILLAGE BLVD.
 CONT: SOURCE REFRIGARATION
 TEL: (904)612-3627
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 07/2015
 ACTION: DENIED
  
 1) STRUCTURAL CALCULATIONS BY CHARLES MOSS FOR HILL
 PHONIX, JOB PUBLIX VILLAGE COMMONS STORE # 1497ROOF TOP
 MECHANICAL CENTER 9'-6" X 58'-0" X 8'-11". ONLY THE
 FIRST PAGE OF THE DOCUMENT IS SIGNED AND SEALED, NO
 INDEX SHEET LISTING HOW MANY PAGES ARE COVERED BY THE
 COVERSHEET. FLORIDA ADMINISTRATIVE STATUTE
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE
 COVERED UNDER THE COVER SHEET OR INDEX SHEET.
  
 2) THERE IS A SECOND DOCUMENT MECHANICAL CENTER CURB
 CONNECTIONS BUT THERE IS NO IDENTIFICATION AS TO WHO
 THE AUTHOR OF THIS DOCUMENT IS, THERE IS MULTPLE PAGES
 TO THIS DOCUMENT.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS.
  
 3) THE PLANS SUBMITTED FOR THE MECHANICAL CENTER APPEAR
 TO NOT BE COMPLETE ONLY PARTIAL PLANS.
 SHEET 1 LIST SHEET 1 OF 2
 SHEET 2 LIST SHEET 1 OF 5
 SHEET 3 LIST SHEET 2 OF 3
 SHEET 4 LIST SHEET 3OF 3
 SHEET 5 LIST SHEET 4 OF 4
  
 WE NORMALLY SEE STATE APPROVED PLANS LIST HOW MANY
 SHEETS ARE WITHIN TTHE DOCUMENT BUT THE NUMBERING IS
 CONSISTANT, A 1-4, E 1-3, OR S1-6 THE WAY THE SHEETS
 ARE NUMBERED WE ARE NOT CERTAIN OF HOW MANY SHEETS ARE
 MISSING? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) THE BUBLIX LOCATION WHERE THIS MECHANICAL CENTER IS
 BEING INSTALLED, THE DESIGNER OF RECORD HAS ELECTED TO
 DESIGN THE BUILDING AS A BUILDING TYPE IIB. THE PLANS
 DO INDICATE THE FLOOR DECK AND ROOF DECK ARE FIRE
 RETARDANT TREATED PLYWOOD SUBSHEATHING. PLEASE INDICATE
 WHERE I CAN FIND THE END WALLS AND SIDE WALLS ALSO HAVE
 FIRE RESISTANT TREATED PLYWOOD. SEE 2010 FBC-B 603.1.1.
  
 5) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (C) PANEL WALLS, WALL LOUVERS, SUBMITTED MIAMI-DADE NOA
 12-0830.08, NOT REVIEWED BY THE DESIGNER OF RECORD.
 (D) ROOFING PRODUCTS AND ASSEMBLIES NO REPORTS
 SUBMITTED.
  
 5A) SUBMITTED DOOR BROCHURE FROM PREMIER SEVERE
 WINDSTORM RATED FOOR & FRAME, PLEASE PROVIDE THE TEST
 REPORT IN COMPLIANCE WITH 2010 FBC-B 1715.3. I DO NOT
 SEE WHERE PREMIER DOORS HAS ANY PRODUCT LISTED WITH
 MIAMI-DADE OR FLORIDA WEBSITE. WE WILL REVIEW ANY
 REPORTS FROM A NATIONALLY RECONIZED AGENCY. WE DO SEE
 ICC REPORTS OR THE OLDER LEGACY REPORTS.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 SHOP DRAWING STAMP OF APPROVED.
  
 7) THE BIG ISSUE IS THIS UNIT WAS BUILT OUT OF STATE,
 NOT UNDER ANY STATE APPROVAL SYSTEM WHERE THERE IS A
 3RD PARTY SYSTEM PROVIDING CERTIFICATION THAT THIS UNIT
 COMPLIES WITH THE 2010 FBC FAMILY OF CODES. IF YOU HAVE
 A 3RD PARTY WHO IS INDEPENDENT THAT IS IN THE
 MANUFACTURING PLANT AS THE UNIT IS BEING BUILT PLEASE
 PROVIDE DOCUMENTATION AS OF SUCH. IF NOT THE PLANS
 SUBMITTED WILL NOT BE SUFFICIENT ENOUGH FOR OUR
 INSPECTORS TO BE ABLE VERIFY CODE COMPLIANCE AT THE
 SITE. ADDITIONAL INFORMATION WILL BE REQUIRED, NOT JUST
 STRUCTURAL CALCULATIONS.
  
 8) A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  