| 2015-10-07 13:59:45 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15100053 |
| | W. P. B. PERMIT: 15050527 UNDER THE 2010 FBC |
| | ADD: 831 VILLAGE BLVD. |
| | CONT: SOURCE REFRIGARATION |
| | TEL: (904)612-3627 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. OCT. 07/2015 |
| | ACTION: DENIED |
| | |
| | 1) STRUCTURAL CALCULATIONS BY CHARLES MOSS FOR HILL |
| | PHONIX, JOB PUBLIX VILLAGE COMMONS STORE # 1497ROOF TOP |
| | MECHANICAL CENTER 9'-6" X 58'-0" X 8'-11". ONLY THE |
| | FIRST PAGE OF THE DOCUMENT IS SIGNED AND SEALED, NO |
| | INDEX SHEET LISTING HOW MANY PAGES ARE COVERED BY THE |
| | COVERSHEET. FLORIDA ADMINISTRATIVE STATUTE |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE |
| | COVERED UNDER THE COVER SHEET OR INDEX SHEET. |
| | |
| | 2) THERE IS A SECOND DOCUMENT MECHANICAL CENTER CURB |
| | CONNECTIONS BUT THERE IS NO IDENTIFICATION AS TO WHO |
| | THE AUTHOR OF THIS DOCUMENT IS, THERE IS MULTPLE PAGES |
| | TO THIS DOCUMENT. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS. |
| | |
| | 3) THE PLANS SUBMITTED FOR THE MECHANICAL CENTER APPEAR |
| | TO NOT BE COMPLETE ONLY PARTIAL PLANS. |
| | SHEET 1 LIST SHEET 1 OF 2 |
| | SHEET 2 LIST SHEET 1 OF 5 |
| | SHEET 3 LIST SHEET 2 OF 3 |
| | SHEET 4 LIST SHEET 3OF 3 |
| | SHEET 5 LIST SHEET 4 OF 4 |
| | |
| | WE NORMALLY SEE STATE APPROVED PLANS LIST HOW MANY |
| | SHEETS ARE WITHIN TTHE DOCUMENT BUT THE NUMBERING IS |
| | CONSISTANT, A 1-4, E 1-3, OR S1-6 THE WAY THE SHEETS |
| | ARE NUMBERED WE ARE NOT CERTAIN OF HOW MANY SHEETS ARE |
| | MISSING? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4) THE BUBLIX LOCATION WHERE THIS MECHANICAL CENTER IS |
| | BEING INSTALLED, THE DESIGNER OF RECORD HAS ELECTED TO |
| | DESIGN THE BUILDING AS A BUILDING TYPE IIB. THE PLANS |
| | DO INDICATE THE FLOOR DECK AND ROOF DECK ARE FIRE |
| | RETARDANT TREATED PLYWOOD SUBSHEATHING. PLEASE INDICATE |
| | WHERE I CAN FIND THE END WALLS AND SIDE WALLS ALSO HAVE |
| | FIRE RESISTANT TREATED PLYWOOD. SEE 2010 FBC-B 603.1.1. |
| | |
| | 5) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (C) PANEL WALLS, WALL LOUVERS, SUBMITTED MIAMI-DADE NOA |
| | 12-0830.08, NOT REVIEWED BY THE DESIGNER OF RECORD. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES NO REPORTS |
| | SUBMITTED. |
| | |
| | 5A) SUBMITTED DOOR BROCHURE FROM PREMIER SEVERE |
| | WINDSTORM RATED FOOR & FRAME, PLEASE PROVIDE THE TEST |
| | REPORT IN COMPLIANCE WITH 2010 FBC-B 1715.3. I DO NOT |
| | SEE WHERE PREMIER DOORS HAS ANY PRODUCT LISTED WITH |
| | MIAMI-DADE OR FLORIDA WEBSITE. WE WILL REVIEW ANY |
| | REPORTS FROM A NATIONALLY RECONIZED AGENCY. WE DO SEE |
| | ICC REPORTS OR THE OLDER LEGACY REPORTS. |
| | |
| | 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | SHOP DRAWING STAMP OF APPROVED. |
| | |
| | 7) THE BIG ISSUE IS THIS UNIT WAS BUILT OUT OF STATE, |
| | NOT UNDER ANY STATE APPROVAL SYSTEM WHERE THERE IS A |
| | 3RD PARTY SYSTEM PROVIDING CERTIFICATION THAT THIS UNIT |
| | COMPLIES WITH THE 2010 FBC FAMILY OF CODES. IF YOU HAVE |
| | A 3RD PARTY WHO IS INDEPENDENT THAT IS IN THE |
| | MANUFACTURING PLANT AS THE UNIT IS BEING BUILT PLEASE |
| | PROVIDE DOCUMENTATION AS OF SUCH. IF NOT THE PLANS |
| | SUBMITTED WILL NOT BE SUFFICIENT ENOUGH FOR OUR |
| | INSPECTORS TO BE ABLE VERIFY CODE COMPLIANCE AT THE |
| | SITE. ADDITIONAL INFORMATION WILL BE REQUIRED, NOT JUST |
| | STRUCTURAL CALCULATIONS. |
| | |
| | 8) A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |