| 2016-06-21 18:09:27 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| | |
| | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS |
| | |
| | (1) PROVIDE MECHANICAL PLANS. |
| | (2) SHOW DUCT SIZES, SUPPLY OUTLET SIZES AND CFM |
| | QUANTITIES. |
| | (3) DIFFERENTIATE WHAT IS EXISTING AND WHAT IS NEW. |
| | (4) PROVIDE EXISTING AHU EQUIPMENT SCHEDULE (TO INCLUDE |
| | TOTAL CFM). |
| | (5) PROVIDE EXHAUST DUCT SIZES FOR KITCHEN EXHAUST. |
| | (6) HAVE ALL MANUFACTURER SPECIFICATION DOCUMENTATION |
| | FOR KITCHEN EXHAUST AT JOBSITE FOR INSPECTOR TO VERIFY |
| | INSTALLATION. |
| | |
| | M1503.4 MAKEUP AIR REQUIRED. |
| | EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF |
| | 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED |
| | WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE |
| | EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE |
| | EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE |
| | AUTOMATICALLY CONTROLLED TO START AND OPERATE |
| | SIMULTANEOUSLY WITH THE EXHAUST SYSTEM. |
| | |
| | EXCEPTION: IN A SINGLE-FAMILY DWELLING, MAKE-UP AIR IS |
| | NOT REQUIRED FOR RANGE HOOD EXHAUST SYSTEMS CAPABLE OF |
| | EXHAUSTING: |
| | (A) FOUR HUNDRED CUBIC FEET PER MINUTE OR LESS; OR |
| | (B) MORE THAN 400 CUBIC FEET PER MINUTE BUT NO MORE |
| | THAN 800 CUBIC FEET PER MINUTE IF THERE ARE NO GRAVITY |
| | VENT APPLIANCES WITHIN THE CONDITIONED LIVING SPACE OF |
| | THE STRUCTURE. |
| | |
| | FLORIDA ENERGY CODE FBC 2014 |
| | |
| | PROVIDE (2) SETS OF SIGNED ENERGY CALCULATIONS (FORM |
| | R405-2014 AND HEAT LOAD CALCULATIONS). ONLY ONE |
| | PROVIDED |
| | |
| | |