| 2016-05-31 14:14:14 | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-7918 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 3RD REVIEW |
| | DATE: 3/31/16 |
| | ACTION: FAILED |
| | |
| | 1. PROVIDE PRODUCT APPROVALS FOR ALL NEW WINDOWS AND |
| | DOORS SHOWN ON PLANS SUBJECT TO WIND LOADS. |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY |
| | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, |
| | WINDOW, AND DOOR SUBMITTALS. |
| | |
| | 2. THE PLAN APPEARS TO INCLUDE THE CONDITIONING OF A |
| | 297 SF AREA OF THE RESIDENCE IDENTIFIED AS A DEN BUT ON |
| | RECORD AS A PORCH. THE PLAN ASSOCIATED WITH THE WINDOW |
| | REPLACEMENT PERMIT 10060887 COMPLETED IN 2010 DOES NOT |
| | SHOW THE CONSTRUCTION OF WALLS AND WINDOWS AS |
| | CONSISTENT WITH THE PROPOSED PLAN. |
| | |
| | PROOF OF COMPLIANCE MAY BE REQUIRED FOR PREVIOUSLY |
| | COMPLETED UN-PERMITTED WORK. |
| | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| | TEST REPORTS AS PROOF OF COMPLIANCE. PLEASE BE ADVISED |
| | THE INSPECTOR MAY REQUIRE PREVIOUSLY COMPLETED WORK TO |
| | BE MADE ACCESSIBLE AND OPEN FOR INSPECTION OR REQUIRE |
| | ADDITIONAL DOCUMENTATION FOR ALL CONCEALED WORK |
| | PREVIOUSLY COMPLETED PURSUANT TO FBC 110 & FBC 117. |
| | |
| | 3. MECHANICAL PERMIT MAY BE REQUIRED. |
| | |
| | 4. PROVIDE MECHANICAL PLAN TO SHOW SUPPLY DUCTS PER FBC |
| | - R M16. |
| | |
| | 5. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED. |
| | CONTACT THE PBC IMPACT FEE OFFICE @ 233-5025. UPON |
| | APPROVAL, YOU MAY CHECK OUT ONE PLAN AND TAKE TO THAT |
| | OFFICE FOR REVIEW. PLEASE RETURN STAMPED WITH A COPY OF |
| | RECEIPT AS APPLICABLE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |