| 2015-10-20 11:30:23 | 1ST REVIEW: FBC 2014 5TH ED. |
| | |
| | PLEASE SEE NOTES IN BUILDING REVIEW AS TO THE CONFLICT |
| | BETWEEN THE PROPOSED PLAN WHICH DESIGNATES THE 297 SF |
| | PORCH AS A DEN. PLEASE PROVIDE AN ELECTRICAL PLAN FOR |
| | THE AREA DESIGNATED AS A DEN AND REGARDING SMOKE |
| | DETECTORS AS FOLLOWS: EXISTING OR PROPOSED ELECTRICAL |
| | OUTLETS AND LIGHTING TO DEMONSTRATE COMPLIANCE WITH THE |
| | FOLLOWING: |
| | |
| | FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES. |
| | IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE LISTED |
| | TAMPER-RESISTANT RECEPTACLES. |
| | |
| | FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| | BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER |
| | INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. |
| | |
| | FBCRE3901.2.2 SPACING. |
| | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| | SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE |
| | OUTLET. |
| | |
| | E3903.3 ADDITIONAL LOCATIONS. |
| | AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET |
| | SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE |
| | EXTERIOR SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE |
| | LEVEL ACCESS. |
| | |
| | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO |
| | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |
| | (561) 805-6710 |
| | [email protected] |
| | |