| Plan Review Notes For Permit 15100027 |
| Permit Number |
15100027 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-08 15:07:47 | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE DETAIL ON ACCESSIBILITY FOR WATER | | | FOUNTAIN THE DETAIL ON SHEET A13.1 | | | PER WPB AMEND. 107.2.1 | | | 2. SHEET G1.1 UNDER PLUMBING FIXTURES PUBLIC ACCESS NOT | | | REQUIRED ,PLEASE SHOW TRAVEL DISTANCE NOT TO EXCEED 300 | | | FT. FROM MAIN ENTRANCE OF ANY STORE OR TENANT SPACE. TO | | | PUBLIC BATHROOMS | | | PER FBC P SEC 403.3.4 | | | 3.SHEET G1.1 UNDER PLUMBING FIXTURES SERVICE SINK NOT | | | REQUIRED .FBC P TABLE 403.1 MINIMUM NUMBER OF REQUIRED | | | PLUMBING FIXTURES. SHOWS A SERVICE SINK IS REQUIRED. | | | PLEASE CLARIFY. | | | PER. WPB AMEND 107.2.1 | | | 4. IS THE WATER FOUNTAIN EXISTING IF NOT PLEASE | | | PROVIVED RISER DIAGRAM. | | | PER WPB AMEND. 107.3.5.1.3(13) |
|