2015-10-08 16:53:021ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100027
 10/8/15
  
 1) SHEET M1.1: REFER TO SECTION 606.2.1 RETURN AIR
 SYSTEMS.
 SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR
 SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM
 (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF
 ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR
 CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND
 APPLIANCES.
 PLEASE REVISE THE PLAN TO SHOW A DUCT SMOKE DETECTOR IN
 THE RETURN AIR SYSTEM AND PROVIDE DETAILS INDICATING
 COMPLIANCE WITH-
 A) 606.4 CONTROLS OPERATION.
 UPON ACTIVATION, THE SMOKE DETECTORS SHALL SHUT DOWN
 ALL OPERATIONAL CAPABILITIES OF THE AIR DISTRIBUTION
 SYSTEM IN ACCORDANCE WITH THE LISTING AND LABELING OF
 APPLIANCES USED IN THE SYSTEM. AIR DISTRIBUTION SYSTEMS
 THAT ARE PART OF A SMOKE CONTROL SYSTEM SHALL SWITCH TO
 THE SMOKE CONTROL MODE UPON ACTIVATION OF A DETECTOR.
 B) 606.4.1 SUPERVISION.
 THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO A FIRE
 ALARM SYSTEM WHERE A FIRE ALARM SYSTEM IS REQUIRED BY
 THE FLORIDA FIRE PREVENTION CODE. THE ACTUATION OF A
 DUCT SMOKE DETECTOR SHALL ACTIVATE A VISIBLE AND
 AUDIBLE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION.
 2) EXHAUST SYSTEMS ARE REQUIRED FOR THE FITTING ROOMS
 AT A RATE OF .25 CFM/SQ.FT. REFER TO TABLE 403.3 AND
 REVISE THE PLAN ACCORDINGLY.
 3) SHUTOFF DAMPER CONTROLS ARE REQUIRED THAT WILL
 AUTOMATICALLY SHUT OFF THE OUTSIDE AIR SUPPLY WHEN THE
 SYSTEM OR SPACE IS NOT IN USE- REFER TO SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER