2015-12-31 13:48:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100011
 ADD: 700 S. ROSEMARY AVE. SUITE # 232
 CONT: TBD
 TEL: (856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. DEC. 31/ 2015
 ACTION: DENIED
  
 1-7) COMPLIED
  
 8) REPETE COMMENT/ PLANS DID SHOULD COMPLIANCE. SHEET
 A2 & A7 BOTH SHOW A 21 INCH TALL STAGE OR RAISED
 PLATFORM, THE STAGE SHOWS 3 RISERS AND A RAMP THAT IS
 3? -10? IN LENGTH AND IS ONLY 2?-11? WIDE WITH NO HAND
 RAILS OR EDGE PROTECTION. . PLEASE SHOW COMPLIANCE WITH
 2014 FBC-ACCESSIBILITY CODE :
  
 8.1) 405.2 SLOPE. RAMP RUNS SHALL HAVE A RUNNING SLOPE
 NOT STEEPER THAN 1:12.
  
 .8.2) 405.5 CLEAR WIDTH. THE CLEAR WIDTH OF A RAMP RUN
 AND, WHERE HANDRAILS ARE PROVIDED, THE CLEAR WIDTH
 BETWEEN HANDRAILS SHALL BE 36 INCHES (915 MM) MINIMUM.
  
 8.3) 405.7 LANDINGS. RAMPS SHALL HAVE LANDINGS AT THE
 TOP AND THE BOTTOM OF EACH RAMP RUN. LANDINGS SHALL
 COMPLY WITH 405.7.
  
 8.4) 405.8 HANDRAILS. RAMP RUNS WITH A RISE GREATER
 THAN 6 INCHES (150 MM) SHALL HAVE HANDRAILS COMPLYING
 WITH 505.
  
 8.5) 405.9 EDGE PROTECTION. EDGE PROTECTION COMPLYING
 WITH 405.9.1 OR 405.9.2 SHALL BE PROVIDED ON EACH SIDE
 OF RAMP RUNS AND AT EACH SIDE OF RAMP LANDINGS.
  
 9) COMPLIED.
  
 10) 3RD REQUEST/SEMI-COMPLIED. SHEET A2 AND A7 BOTH
 INDICATE NEW HINGED ENTRY DOORS AND HORIZONTAL SLIDING
 DOORS. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SLIDING SUBMITTED BUT NOT IN
 COMPLIANCE WITH COMMENT ( 10A).
 (31)(A) SWING DOORS TWO ISSUES:
 FOR THE NEW SWING DOOR JUST SOUTH OF THE ENTRY DOORS NO
 PRODUCT APPROVAL WAS SUBMITTED.
 FOR THE ENTRY DOORS TO BE RE-USED PLEASE PROVIDE
 DOCUMENTATION OF CODE COMPLIANCE FOR WIND
 AS WELL AS LARGE MISSILE IMPACT TESTING AND ANCHORING
 OF THE FRAME FOR THE MAIN WIND FORCE
 RESISTING SYSTEM.
  
 10A)3RD REQUEST. PGT SERIES SGD-770 ALUMINUM SLIDING
 GLASS DOORS NOA 14-0128.11 THE CONTRACTOR HAS NOT
 IDENTIFIED WHICH SYSTEM IS TO BE INSTALLED. IN THE CASE
 OF ALL TABLES 1,LIMITS THE DESIGN PRESSURES DEPENDING
 ON THE SILL HEIGHT, PLEASE CIRCLE THE APPROPRIATE JOB
 INSTALLATION.
 THE DESIGNER OF RECORD IS SUPPOSE TO REVIEW THE PRODUCT
 APPROVAL AFTER THE CONTRACTOR HAS CIRCLED THE TYPE OF
 SILL TO BE INSTALLED. THE 2 ? INCH SILL ONLY HAS A
 +46.67 PSF PRESSURE RATING. THE OTHER ISSUE MAYBE
 ACCESSIBILITY AND AS WELL AS EGRESS.
  
 11) 3RD REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12-14) COMPLIED.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  