| 2015-11-19 13:51:50 | 2ND REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15100011 |
| | 11/19/15 |
| | |
| | SEVERAL COMMENTS FROM THE 1ST REVIEW WERE NOT |
| | ADDRESSED. I AM RE-PRINTING THEM BELOW FOR RESPONSE. |
| | |
| | 1) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH |
| | C101.2 AND C101.4.3 FBC-14 ENERGY CONSERVATION. |
| | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING |
| | 809.1 RECONFIGURED OR CONVERTED SPACES. |
| | ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND ALL |
| | SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE IN |
| | ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR |
| | MECHANICAL VENTILATION IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, MECHANICAL. |
| | EXCEPTION: EXISTING MECHANICAL VENTILATION SYSTEMS |
| | SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 809.2. |
| | 809.2 ALTERED EXISTING SYSTEMS. |
| | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL |
| | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR |
| | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER |
| | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR |
| | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION |
| | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF |
| | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY |
| | PROCEDURE OF ASHRAE 62. |
| | PLEASE PROVIDE VENTILATION CALCULATIONS IN COMPLIANCE |
| | WITH TABLE 403.3 FBC-14 MECHANICAL. THE CALCULATIONS |
| | SHALL INDICATE THE AMOUNT OF OUTSIDE AIR CFM'S |
| | REQUIRED, AND THE AMOUNT OF OUTSIDE AIR CFM'S BEING |
| | PROVIDED EITHER BY THE EXISTING OR MODIFIED HVAC |
| | SYSTEMS. |
| | 3) PLEASE PROVIDE MECHANICAL PLANS INDICATING ALL |
| | PROPOSED ALTERATIONS TO THE EXISTING HVAC SYSTEMS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |