| 2015-11-19 08:58:29 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100011 |
| | ADD: 700 S. ROSEMARY AVE. SUITE # 232 |
| | CONT: TBD |
| | TEL: (856-6655 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. NOV. 19/ 2015 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED |
| | |
| | 4) SHEET A7 THE LIFE SAFETY PLAN SHOWS EGRESS PATHS |
| | THROUGH MANUALLY SLIDING GLASS DOORS. THERE APPEARS TO |
| | BE (2) AREAS THAT HAVE SLIDING GLASS DOORS, THE SLIDING |
| | GLASS DOORS BETWEEN BAR AREA 12 AND BAR AREA 22, IT |
| | APPEARS THIS AREA IS TRYING TO BE USED AS A EGRESS |
| | PATH. PLEASE REVIEW 1008.1.2. EGRESS DOORS ARE TO BE |
| | PIVOTED OR SIDE HINGED SWING DOORS. THE PLAN DOES NOT |
| | SHOW A PATH OF EGRESS FOR THIS OCCUPANT LOAD. SHEET A4 |
| | IT IS NOT CLEAR IF THERE IS A RAILING AT THE TENANT |
| | WALL LINE IN HIS AREA? |
| | |
| | 5) 2ND REQUEST. COMMENT FROM 1ST REVIEW. SHEET A7 THE |
| | OCCUPANT LOAD AROUND BAR # 12 THE MAIN BAR TO THE MAIN |
| | ENTRY HAS APPROXIMATELY 50 OCCUPANT LOAD COUNTING THE |
| | OCCUPANT LOAD BEHIND THE BAR. PLEASE SHOW COMPLIANCE |
| | WITH: |
| | |
| | 1028.10.1.2 SEATING AT TABLE AISLE ACCESS WAY LENGTH. |
| | THE LENGTH OF TRAVEL ALONG THE AISLE ACCESS WAY SHALL |
| | NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT |
| | WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS OF |
| | EGRESS TRAVEL TO SEPARATE EXITS. |
| | COMMON PATH OF TRAVEL CAN NOT CONVERGE BACK TO THE SAME |
| | ROUTE TO EXIT. |
| | |
| | 6)2ND REQUEST. SHEET A7 EXTERIOR DINING ROOM 20 WITH |
| | THE NEW TABLE LAY OUT STILL HAS ISSUES WITH COMMON PATH |
| | OF TRAVEL. THE COLUMN NEXT TO THE TABLE THE SEAT JUST |
| | TO THE SOUTH OF THE COLUMN HAS TO TRAVEL APPROXIMATELY |
| | 35 FEET BEFORE THERE ARE (2) CHOICES IN EXITING, THE |
| | COMMON PATH OF TRAVEL HAS BEEN EXCEEDED. |
| | |
| | 1028.10.1.2 SEATING AT TABLE AISLE ACCESS WAY LENGTH. |
| | THE LENGTH OF TRAVEL ALONG THE AISLE ACCESS WAY SHALL |
| | NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT |
| | WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS OF |
| | EGRESS TRAVEL TO SEPARATE EXITS. |
| | |
| | 7) SHEET A7 THE EXTERIOR BAR 22 IT APPEARS THERE ARE 8 |
| | BAR STOOLS NEXT TO THE SLIDING GLASS DOORS THAT DOES |
| | NOT HAVE A 32 INCH EGRESS DOOR OPENING. 2014 FBC-B |
| | 1008.1.1 SIZE OF DOOR. THE LIFE SAFETY PLAN DOES NOT |
| | SHOW HOW THE OCCUPANTS OF THE 8 BAR STOOLS ARE EXITING |
| | THIS AREA? TO THE SOUTH SIDE OF THE 8 BAR STOOLS THE |
| | FIRST GENERATION OF PLANS SHOWED WHAT APPEARED TO BE |
| | EITHER A SIGN OR SLIDING GLASS DOOR. (2) ISSUES EGRESS |
| | FROM THIS AREA, THE SECOND ISSUE IS OCCUPANT LOAD |
| | GREATER THAN 10 CANNOT USE A SLIDING GLASS DOOR AS A |
| | MEANS OF EGRESS. |
| | |
| | 8) COMPLIED. SHEET A2 & A7 BOTH SHOW A 14 INCH TALL |
| | STAGE OR RAISED PLATFORM, THE STAGE SHOWS A STEP BUT NO |
| | VERTICAL ACCESSIBILITY. PLEASE SHOW COMPLIANCE WITH |
| | 2014 FBC-ACCESSIBILITY CODE 201.1.1. |
| | |
| | 9) 2ND REQUEST. COMMENT FROM 1ST REVIEW. THE OCCUPANT |
| | LOAD FOR THE DINING PORTION OF THE TENANT SPACE IS 287 |
| | X 0.05= 15 ACCESSIBLE SEATS REQUIRED. |
| | SHEET A7 INDICATES THERE IS 11 ACCESSIBLE LOCATIONS FOR |
| | WHEELCHAIR SETTING, THEN IN SMALLER LETTERING THE PLANS |
| | INDICATE ONLY EIGHT AND THERE IS ONLY 8 ON THE PLANS. |
| | 2014 FBC-ACCESSIBILITY 226.1. WITH THE INTERIOR AND |
| | EXTERIOR SEATING THE OCCUPANT SEAT COUNT IS 212 |
| | REQUIRING 11 ACCESSIBLE SEATING AREAS. |
| | |
| | 10) 2ND REQUEST/SEMI-COMPLIED. SHEET A2 AND A7 BOTH |
| | INDICATE NEW HINGED ENTRY DOORS AND HORIZONTAL SLIDING |
| | DOORS. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. SLIDING AND SWING DOORS |
| | |
| | 10A) PGT SERIES SGD-770 ALUMINUM SLIDING GLASS DOORS |
| | NOA 14-0128.11 THE CONTRACTOR HAS NOT IDENTIFIED WHICH |
| | SYSTEM IS TO BE INSTALLED. IN THE CASE OF ALL TABLES |
| | 1,2 & 3 IN ALL CASES TABLE A LIMITS THE DESIGN |
| | PRESSURES PLEASE CIRCLE THE APPROPRIATE JOB |
| | INSTALLATION. |
| | |
| | |
| | 11) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | |
| | 12)2ND REQUEST, SEMI-COMPLIED. MISSING WIND DESIGN |
| | CRITERIA FOR THE NEW OPENINGS. 2014 FBC-B 1603.1.4 WIND |
| | DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO WIND |
| | LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS |
| | GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM |
| | OF THE STRUCTURE: |
| | |
| | COMPLIED. 12.1. ULTIMATE DESIGN WIND SPEED, VULT, |
| | (3-SECOND GUST), MILES PER HOUR (KM/HR) AND NOMINAL |
| | DESIGN WIND SPEED, VASD, AS DETERMINED IN ACCORDANCE |
| | WITH SECTION 1609.3.1. |
| | |
| | COMPLIED. 12.2. RISK CATEGORY. |
| | |
| | 2ND REQUEST. 12.3. WIND EXPOSURE. APPLICABLE WIND |
| | DIRECTION IF MORE THAN ONE WIND EXPOSURE IS UTILIZED. |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. THE COVERSHEET LIST THE EXPOSURE AND HEIGHT |
| | COEFFICIENT AS 1.49. THIS IS EQUAL TO A MEAN ROOF |
| | HEIGHT OF 40 FT. SHEET A.4 INDICATES THE MEAN ROOF |
| | HEIGHT OF 57 FT. OR A COEFFICIENT OF 1.60 FOR A |
| | MULTIPLIER. |
| | |
| | COMPLIED.12.4 APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 12.5. 2ND REQUEST. DESIGN WIND PRESSURES TO BE USED FOR |
| | EXTERIOR COMPONENT AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THE |
| | STRUCTURE, PSF (KN/ M2). |
| | |
| | 13) COMPLIED. SHEET A2 AND A7 SHOW WOOD BARRELS SET OUT |
| | FROM THE WALL AS A WALL FINISH. PLEASE SHOW COMPLIANCE |
| | WITH [F] 806.1.2 COMBUSTIBLE DECORATIVE MATERIALS. THE |
| | PERMISSIBLE AMOUNT OF DECORATIVE MATERIALS MEETING THE |
| | FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 |
| | SHALL NOT EXCEED 10 PERCENT OF THE SPECIFIC WALL OR |
| | CEILING AREA TO WHICH IT IS ATTACHED. |
| | |
| | 14) COMPLIED. SHEET A2 & A7 BOTH SHOW DROPPED WOOD |
| | FRAMING FOR A DECORATIVE CEILING, PLEASE SHOW |
| | COMPLIANCE WITH: |
| | 803.1.1 INTERIOR WALL AND CEILING FINISH MATERIALS. |
| | INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE |
| | CLASSIFIED IN ACCORDANCE WITH ASTM E 84 OR UL 723. SUCH |
| | INTERIOR FINISH MATERIALS SHALL BE GROUPED IN THE |
| | FOLLOWING CLASSES IN ACCORDANCE WITH THEIR FLAME SPREAD |
| | AND SMOKE-DEVELOPED INDEXES. |
| | |
| | CLASS A:FLAME SPREAD INDEX 0-25; SMOKE- |
| | DEVELOPED INDEX 0-450. |
| | |
| | CLASS B:=FLAME SPREAD INDEX 26-75; SMOKE- |
| | DEVELOPED INDEX 0-450. |
| | |
| | CLASS C:FLAME SPREAD INDEX 76-200; SMOKE- |
| | DEVELOPED INDEX 0-450. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |