Plan Review Notes
Plan Review Notes For Permit 15100011
Permit Number 15100011
Review Stop B
Sequence Number 2
Notes
Date Text
2015-11-19 08:58:29BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100011
 ADD: 700 S. ROSEMARY AVE. SUITE # 232
 CONT: TBD
 TEL: (856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. NOV. 19/ 2015
 ACTION: DENIED
  
 1-3) COMPLIED
  
 4) SHEET A7 THE LIFE SAFETY PLAN SHOWS EGRESS PATHS
 THROUGH MANUALLY SLIDING GLASS DOORS. THERE APPEARS TO
 BE (2) AREAS THAT HAVE SLIDING GLASS DOORS, THE SLIDING
 GLASS DOORS BETWEEN BAR AREA 12 AND BAR AREA 22, IT
 APPEARS THIS AREA IS TRYING TO BE USED AS A EGRESS
 PATH. PLEASE REVIEW 1008.1.2. EGRESS DOORS ARE TO BE
 PIVOTED OR SIDE HINGED SWING DOORS. THE PLAN DOES NOT
 SHOW A PATH OF EGRESS FOR THIS OCCUPANT LOAD. SHEET A4
 IT IS NOT CLEAR IF THERE IS A RAILING AT THE TENANT
 WALL LINE IN HIS AREA?
  
 5) 2ND REQUEST. COMMENT FROM 1ST REVIEW. SHEET A7 THE
 OCCUPANT LOAD AROUND BAR # 12 THE MAIN BAR TO THE MAIN
 ENTRY HAS APPROXIMATELY 50 OCCUPANT LOAD COUNTING THE
 OCCUPANT LOAD BEHIND THE BAR. PLEASE SHOW COMPLIANCE
 WITH:
  
 1028.10.1.2 SEATING AT TABLE AISLE ACCESS WAY LENGTH.
 THE LENGTH OF TRAVEL ALONG THE AISLE ACCESS WAY SHALL
 NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT
 WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS OF
 EGRESS TRAVEL TO SEPARATE EXITS.
 COMMON PATH OF TRAVEL CAN NOT CONVERGE BACK TO THE SAME
 ROUTE TO EXIT.
  
 6)2ND REQUEST. SHEET A7 EXTERIOR DINING ROOM 20 WITH
 THE NEW TABLE LAY OUT STILL HAS ISSUES WITH COMMON PATH
 OF TRAVEL. THE COLUMN NEXT TO THE TABLE THE SEAT JUST
 TO THE SOUTH OF THE COLUMN HAS TO TRAVEL APPROXIMATELY
 35 FEET BEFORE THERE ARE (2) CHOICES IN EXITING, THE
 COMMON PATH OF TRAVEL HAS BEEN EXCEEDED.
  
 1028.10.1.2 SEATING AT TABLE AISLE ACCESS WAY LENGTH.
 THE LENGTH OF TRAVEL ALONG THE AISLE ACCESS WAY SHALL
 NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT
 WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS OF
 EGRESS TRAVEL TO SEPARATE EXITS.
  
 7) SHEET A7 THE EXTERIOR BAR 22 IT APPEARS THERE ARE 8
 BAR STOOLS NEXT TO THE SLIDING GLASS DOORS THAT DOES
 NOT HAVE A 32 INCH EGRESS DOOR OPENING. 2014 FBC-B
 1008.1.1 SIZE OF DOOR. THE LIFE SAFETY PLAN DOES NOT
 SHOW HOW THE OCCUPANTS OF THE 8 BAR STOOLS ARE EXITING
 THIS AREA? TO THE SOUTH SIDE OF THE 8 BAR STOOLS THE
 FIRST GENERATION OF PLANS SHOWED WHAT APPEARED TO BE
 EITHER A SIGN OR SLIDING GLASS DOOR. (2) ISSUES EGRESS
 FROM THIS AREA, THE SECOND ISSUE IS OCCUPANT LOAD
 GREATER THAN 10 CANNOT USE A SLIDING GLASS DOOR AS A
 MEANS OF EGRESS.
  
 8) COMPLIED. SHEET A2 & A7 BOTH SHOW A 14 INCH TALL
 STAGE OR RAISED PLATFORM, THE STAGE SHOWS A STEP BUT NO
 VERTICAL ACCESSIBILITY. PLEASE SHOW COMPLIANCE WITH
 2014 FBC-ACCESSIBILITY CODE 201.1.1.
  
 9) 2ND REQUEST. COMMENT FROM 1ST REVIEW. THE OCCUPANT
 LOAD FOR THE DINING PORTION OF THE TENANT SPACE IS 287
 X 0.05= 15 ACCESSIBLE SEATS REQUIRED.
 SHEET A7 INDICATES THERE IS 11 ACCESSIBLE LOCATIONS FOR
 WHEELCHAIR SETTING, THEN IN SMALLER LETTERING THE PLANS
 INDICATE ONLY EIGHT AND THERE IS ONLY 8 ON THE PLANS.
 2014 FBC-ACCESSIBILITY 226.1. WITH THE INTERIOR AND
 EXTERIOR SEATING THE OCCUPANT SEAT COUNT IS 212
 REQUIRING 11 ACCESSIBLE SEATING AREAS.
  
 10) 2ND REQUEST/SEMI-COMPLIED. SHEET A2 AND A7 BOTH
 INDICATE NEW HINGED ENTRY DOORS AND HORIZONTAL SLIDING
 DOORS. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SLIDING AND SWING DOORS
  
 10A) PGT SERIES SGD-770 ALUMINUM SLIDING GLASS DOORS
 NOA 14-0128.11 THE CONTRACTOR HAS NOT IDENTIFIED WHICH
 SYSTEM IS TO BE INSTALLED. IN THE CASE OF ALL TABLES
 1,2 & 3 IN ALL CASES TABLE A LIMITS THE DESIGN
 PRESSURES PLEASE CIRCLE THE APPROPRIATE JOB
 INSTALLATION.
  
  
 11) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
  
 12)2ND REQUEST, SEMI-COMPLIED. MISSING WIND DESIGN
 CRITERIA FOR THE NEW OPENINGS. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO WIND
 LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS
 GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM
 OF THE STRUCTURE:
  
 COMPLIED. 12.1. ULTIMATE DESIGN WIND SPEED, VULT,
 (3-SECOND GUST), MILES PER HOUR (KM/HR) AND NOMINAL
 DESIGN WIND SPEED, VASD, AS DETERMINED IN ACCORDANCE
 WITH SECTION 1609.3.1.
  
 COMPLIED. 12.2. RISK CATEGORY.
  
 2ND REQUEST. 12.3. WIND EXPOSURE. APPLICABLE WIND
 DIRECTION IF MORE THAN ONE WIND EXPOSURE IS UTILIZED.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. THE COVERSHEET LIST THE EXPOSURE AND HEIGHT
 COEFFICIENT AS 1.49. THIS IS EQUAL TO A MEAN ROOF
 HEIGHT OF 40 FT. SHEET A.4 INDICATES THE MEAN ROOF
 HEIGHT OF 57 FT. OR A COEFFICIENT OF 1.60 FOR A
 MULTIPLIER.
  
 COMPLIED.12.4 APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 12.5. 2ND REQUEST. DESIGN WIND PRESSURES TO BE USED FOR
 EXTERIOR COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THE
 STRUCTURE, PSF (KN/ M2).
  
 13) COMPLIED. SHEET A2 AND A7 SHOW WOOD BARRELS SET OUT
 FROM THE WALL AS A WALL FINISH. PLEASE SHOW COMPLIANCE
 WITH [F] 806.1.2 COMBUSTIBLE DECORATIVE MATERIALS. THE
 PERMISSIBLE AMOUNT OF DECORATIVE MATERIALS MEETING THE
 FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701
 SHALL NOT EXCEED 10 PERCENT OF THE SPECIFIC WALL OR
 CEILING AREA TO WHICH IT IS ATTACHED.
  
 14) COMPLIED. SHEET A2 & A7 BOTH SHOW DROPPED WOOD
 FRAMING FOR A DECORATIVE CEILING, PLEASE SHOW
 COMPLIANCE WITH:
 803.1.1 INTERIOR WALL AND CEILING FINISH MATERIALS.
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASSIFIED IN ACCORDANCE WITH ASTM E 84 OR UL 723. SUCH
 INTERIOR FINISH MATERIALS SHALL BE GROUPED IN THE
 FOLLOWING CLASSES IN ACCORDANCE WITH THEIR FLAME SPREAD
 AND SMOKE-DEVELOPED INDEXES.
  
 CLASS A:FLAME SPREAD INDEX 0-25; SMOKE-
 DEVELOPED INDEX 0-450.
  
 CLASS B:=FLAME SPREAD INDEX 26-75; SMOKE-
 DEVELOPED INDEX 0-450.
  
 CLASS C:FLAME SPREAD INDEX 76-200; SMOKE-
 DEVELOPED INDEX 0-450.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  