| 2015-11-02 18:20:48 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION |
| | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION |
| | OF THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND |
| | BELOW ARE THE DEFICIENCIES NOTED. |
| | THOUGH THE PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN |
| | ADDRESSED, THE NEW PLANS HAVE A COUPLE OF ITEMS NEEDING |
| | CORRECTION: |
| | |
| | THERE WERE THE SAME PLANS PREVIOUSLY REVIEWED AND |
| | SUBSEQUENTLY DENIED FOR LACK OF ELECTRICAL DATA. YOU |
| | WERE PREVIOUSLY INSTRUCTED TO PROVIDE AN ELECTRICAL |
| | SHEET WITH THE REQUIRED ELECTRICAL INFORMATION. |
| | |
| | 1. NEC 600.5 REQUIRES THAT THERE BE A DEDICATE SIGN |
| | OUTLET AT EVERY PEDESTRIAN ENTRY INTO EVERY COMMERCIAL |
| | ESTABLISHMENT. YOU ARE MISSING THE MAIN ENTRANCE AND |
| | MAYBE EVEN THE REAR DOOR AS IT APPEARS TO BE AN ENTRY |
| | FOR THE PRIVATE PARTY ROOM. |
| | 2. THE SUBMITTED POWER PLAN FAILS TO INCLUDE THE |
| | OUTLETS AND ADDITIONAL LOADS IN THE REAR AND KITCHEN |
| | AREAS. |
| | 3. YOU SHALL SUBMIT A LIGHTING PLAN THAT COMPLIES WITH |
| | THE ENERGY CONSERVATION REQUIREMENTS OF THE FBC-ENERGY |
| | CONSERVATION CODE. YOU SHALL ADDRESS THE LIGHT DENSITY |
| | CHART, MANDATORY SWITCHING REQUIREMENTS AND THE |
| | EFFICIENCY OF THE LUMINAIRES. |
| | 4. ALL RECESSED LUMINARIES SHALL BE IC RATED AND SEALED |
| | TO PREVENT TRANSFER OF AIR FROM THE CONDITIONED AIR |
| | SPACE TO THE NON-CONDITIONED AIR SPACE. |
| | 5. YOU SHALL PROVIDE THE FEEDER DIAGRAM WITH LOAD CALCS |
| | AND CONDUCTOR SIZING AS REQUIRED IN NEC 215.5. |
| | 6. YOU SHALL PROVIDE, FOR EVERY PANEL A CIRCUIT |
| | DIRECTORY AS REQUIRED BY NEC 408.4 FOR EVERY PANEL |
| | WITHIN THE PREMISES. EACH SHALL BE LABELED WITH AN |
| | ARC-FLASH HAZARD WARNING LABEL AS INDICATED IN NEC |
| | 110.16. |
| | 7. FROM THE FLOOR PLAN AS PROVIDE, I CAN?T ACTUALLY |
| | DETERMINE WHAT IS A GLASS WINDOW AND WHAT IS NOT, |
| | THEREFORE KEEP IN MIND THE NEC 210.62 REQUIRES THAT |
| | THERE BE A SHOW WINDOW OUTLET FOR EVERY 12 LINEAR FEET |
| | OF SHOW WINDOW OR MAJOR PORTION THEREOF. |
| | 8. YOU SHALL PROVIDE A ROOF PLAN OR INDICATE WHERE THE |
| | CONDENSING UNITS FOR ALL REFRIGERATION EQUIPMENT ARE |
| | LOCATED. |
| | |
| | IF AT ALL POSSIBLE, TO EXPEDITE THE ELECTRICAL REVIEW |
| | PROCESS, A LESS CLUTTERED ELECTRICAL SHEET DRAWN TO A |
| | LARGER SCALE WILL BE GREATLY APPRECIATED. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | |