2015-10-09 15:57:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100011
 ADD: 700 S. ROSEMARY AVE. SUITE # 232
 CONT: TBD
 TEL: (856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. OCT. 09/ 2014
 ACTION: DENIED
  
 1) SHEET A1 THE DEMOLITION PLAN INDICATES THE EXISTING
 DOUBLE ENTRY DOORS ARE TO BE RELOCATED. BOTH SHEETS A2
 & A7 SHOW NEW DOUBLE ENTRY DOORS, THE DOOR WIDTH BEING
 (2) 2'-0" DOORS. PLEASE COMPLY WITH 2014 FBC-B
 BUILDING. 1008.1.1 SIZE OF DOORS. THE MINIMUM WIDTH OF
 EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT
 LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32
 INCHES (813 MM). CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES
 (1.57 RAD). WHERE THIS SECTION REQUIRES A MINIMUM CLEAR
 WIDTH OF 32 INCHES (813 MM) AND A DOOR OPENING INCLUDES
 TWO DOOR LEAVES WITHOUT A MULLION, ONE LEAF SHALL
 PROVIDE A CLEAR OPENING WIDTH OF 32 INCHES (813 MM).
  
 DISCREPANCY IN PLANS, SHEET A9 INDICATES (2) 3'-0"
 DOORS.
  
 2) SHEET A7 THE LIFE SAFETY PLAN DOES NOT INDICATE WHAT
 THE OCCUPANT LOAD IS FOR THE TENANT SPACE OFFICE AND
 KITCHEN WERE NOT FIGURED INTO THE EQUATION.2014 FBC-B
 TABLE 1004.1.2.
  
 3A) PLEASE PROVIDE ON THE LIFE SAFETY SHEET A7 THE
 ALLOWABLE OCCUPANT LOAD PER EGRESS DOOR. 2014 FBC-B
 1005.3.2 OTHER EGRESS COMPONENTS. THE CAPACITY, IN
 INCHES (MM), OF MEANS OF EGRESS COMPONENTS OTHER THAN
 STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE
 OCCUPANT LOAD SERVED BY SUCH COMPONENT BY A MEANS OF
 EGRESS CAPACITY FACTOR OF 0.2 INCH (5.1 MM) PER
 OCCUPANT.
  
 3B) 2014 FBC-B 1005.5. DISTRIBUTION OF EGRESS CAPACITY.
 WHERE MORE THAN ONE EXIT, OR ACCESS TO MORE THAN ONE
 EXIT, IS REQUIRED, THE MEANS OF EGRESS SHALL BE
 CONFIGURED SUCH THAT THE LOSS OF ANY ONE EXIT, OR
 ACCESS TO ONE EXIT, SHALL NOT REDUCE THE AVAILABLE
 CAPACITY TO LESS THAN 50 PERCENT OF THE REQUIRED
 CAPACITY.
  
 4) SHEET A7 THE LIFE SAFETY PLAN SHOWS EGRESS PATHS
 THROUGH MAUALLY SLIDDING GLASS DOORS. THERE APPEARS TO
 BE (2) AREAS THAT HAVE SLIDDING GLASS DOORS, THE
 SLIDDING GLASS DOORS BETWEEN BAR AREA 12 AND BAR AREA
 20, IT APPEARS THIS AREA IS TRYING TO BE USED AS A
 EGRESS PATH. PLEASE REVIEW 1008.1.2. EGRESS DOORS ARE
 TO BE PIVOTED OR SIDE HINGED SWING DOORS.
  
 5) SHEET A7 THE OCCUPANT LOAD AROUND BAR # 12 THE MAIN
 BAR TO THE MAIN ENTRY HAS APPROXIMATELY 50 OCCUPANT
 LOAD COUNTING THE OCCUPANT LOAD BEHIND THE BAR. PLEASE
 SHOW COMPLIANCE WITH:
  
 1028.10.1.2 SEATING AT TABLE AISLE ACCESSWAY LENGTH.
 THE LENGTH OF TRAVEL ALONG THE AISLE ACCESSWAY SHALL
 NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT
 WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS OF
 EGRESS TRAVEL TO SEPARATE EXITS.
  
 6) SHEET A7 EXTERIOR DINING ROOM 20 HAS A COLUMN NEXT
 TO THE TABLE THE SEAT JUST TO THE SOUTH OF THE COLUMN
 HAS TO TRAVEL APPROXIMATELY 40 FEET BEFORE THERE ARE
 (2) CHOICES IN EXITING, THE COMMON PATH OF TRAVEL HAS
 BEEN EXCEEDED.
  
 1028.10.1.2 SEATING AT TABLE AISLE ACCESSWAY LENGTH.
 THE LENGTH OF TRAVEL ALONG THE AISLE ACCESSWAY SHALL
 NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT
 WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS OF
 EGRESS TRAVEL TO SEPARATE EXITS.
  
 7) SHEET A7 THE EXTERIOR BAR 20 IT APPEARS THERE ARE 8
 BAR STOOLS NEXT TO THE SLIDING GLASS DOORS THAT T DOES
 NOT HAVE A 32 INCH EGRESS DOOR OPENING. 2014 FBC-B
 1008.1.1 SIZE OF DOOR.
  
 8) SHEET A2 & A7 BOTH SHOW A 14 INCH TALL STAGE OR
 RAISED PLATFORM, THE STAGE SHOWS A STEP BUT NO VERTICAL
 ACCESSIBILITY. PLEASE SHOW COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE 201.1.1.
  
 9) SHEET A7 INDICATES THERE IS 11 ACCESSIBLE LOCATIONS
 FOR WHEELCHAIR SETTING, THEN IN SMALLER LETTERING THE
 PLANS INDICATE ONLY EIGHT AND THERE IS ONLY 8 ONTHE
 PLANS. 2014 FBC-ACCESSIBLITY 226.1. WITH THE INTERIOR
 AND EXTERIOR SEATTING THE OCCUPANT SEAT COUNT IS 212
 REQUIRING 11 ACCESSIBLE SEATING AREAS.
  
 10) SHEET A2 AND A7 BOTH INDICATE NEW HINGED ENTRY
 DOORS AND HORIZONTAL SLIDING DOORS. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 11) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 12) MISSING WIND DESIGN CRITERIA FOR THE NEW OPENINGS.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 12.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 12.2. RISK CATEGORY.
  
 12.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 12.4 APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 12.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 13) SHEET A2 AND A7 SHOW WOOD BARRELS SET OUT FROM THE
 WALL AS A WALL FINISH. PLEASE SHOW COMPLIANCE WITH [F]
 806.1.2 COMBUSTIBLE DECORATIVE MATERIALS. THE
 PERMISSIBLE AMOUNT OF DECORATIVE MATERIALS MEETING THE
 FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701
 SHALL NOT EXCEED 10 PERCENT OF THE SPECIFIC WALL OR
 CEILING AREA TO WHICH IT IS ATTACHED.
  
 14) SHEET A2 & A7 BOTH SHOW DROPPED WOOD FRAMING FOR A
 DECRATIVE CEILING, PLEASE SHOW COMPLIANCE WITH:
 803.1.1 INTERIOR WALL AND CEILING FINISH MATERIALS.
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASSIFIED IN ACCORDANCE WITH ASTM E 84 OR UL 723. SUCH
 INTERIOR FINISH MATERIALS SHALL BE GROUPED IN THE
 FOLLOWING CLASSES IN ACCORDANCE WITH THEIR FLAME SPREAD
 AND SMOKE-DEVELOPED INDEXES.
  
 CLASS A:FLAME SPREAD INDEX 0-25; SMOKE-
 DEVELOPED INDEX 0-450.
  
 CLASS B:=FLAME SPREAD INDEX 26-75; SMOKE-
 DEVELOPED INDEX 0-450.
  
 CLASS C:FLAME SPREAD INDEX 76-200; SMOKE-
 DEVELOPED INDEX 0-450.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  