2017-04-06 11:51:311ST REVIEW FBC-2014 MECHANICAL
 PERMIT #15091310
 4/6/17
  
 1) THE SUBMITTED CUT SHEET FOR THE COOLING TOWER DOES
 NOT INDICATE THE UNIT IS A UL 1995 LISTED PRODUCT AS
 REQUIRED BY SECTION 908.1 FBC-14 MECHANICAL, AND
 SECTION M1413.1 FBC-14 RESIDENTIAL. I HAVE INQUIRED
 WITH THE TECHNICAL DEPARTMENT OF PROTEC AND THEY WERE
 NOT ABLE TO PROVIDE ANY INFORMATION IN REGARD. PLEASE
 PROVIDE DOCUMENTATION TO SHOW COMPLIANCE.
  
 2) BASED ON SPECIFICATIONS I HAVE VIEWED ONLINE FOR THE
 TOWER, IT APPEARS THAT THE SELECTED MODEL PC-10 AT 8
 TONS IS OVERSIZED FOR THE SYSTEM WHICH HAS BEEN
 CALCULATED AT APPROXIMATELY 5 TONS OF COOLING- SEE
 SECTION R403.6.1.1 FBC-14 ENERGY CONSERVATION.
  
 3) PROVIDE COMPLIANCE DATA FOR THE COOLING TOWER ON THE
 ENERGYGAUGE FORM R405-2014- SEE TABLE C403.2.3(8).
  
 4) AS PREVIOUSLY REQUESTED PROVIDE ENGINEERING FOR
 ANCHORING THE EQUIPMENT TO RESIST WIND PRESSURES.
 ENGINEERING FROM THE MANUFACTURER IS ACCEPTABLE IF THE
 DESIGN CRITERIA IS COMPLIANTT WITH SECTION R301.2.1
 FBC-14 RESIDENTIAL.
  
 5) PROVIDE THE CLEARANCE DISTANCE FROM THE TOWER TO THE
 BUILDING.
  
 6) INDICATE HOW THE HEAT PUMPS IN THE GARAGE WILL BE
 PROTECTED FROM VEHICULAR DAMAGE
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719