| 2017-04-06 11:51:31 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #15091310 | | | 4/6/17 | | | | | | 1) THE SUBMITTED CUT SHEET FOR THE COOLING TOWER DOES | | | NOT INDICATE THE UNIT IS A UL 1995 LISTED PRODUCT AS | | | REQUIRED BY SECTION 908.1 FBC-14 MECHANICAL, AND | | | SECTION M1413.1 FBC-14 RESIDENTIAL. I HAVE INQUIRED | | | WITH THE TECHNICAL DEPARTMENT OF PROTEC AND THEY WERE | | | NOT ABLE TO PROVIDE ANY INFORMATION IN REGARD. PLEASE | | | PROVIDE DOCUMENTATION TO SHOW COMPLIANCE. | | | | | | 2) BASED ON SPECIFICATIONS I HAVE VIEWED ONLINE FOR THE | | | TOWER, IT APPEARS THAT THE SELECTED MODEL PC-10 AT 8 | | | TONS IS OVERSIZED FOR THE SYSTEM WHICH HAS BEEN | | | CALCULATED AT APPROXIMATELY 5 TONS OF COOLING- SEE | | | SECTION R403.6.1.1 FBC-14 ENERGY CONSERVATION. | | | | | | 3) PROVIDE COMPLIANCE DATA FOR THE COOLING TOWER ON THE | | | ENERGYGAUGE FORM R405-2014- SEE TABLE C403.2.3(8). | | | | | | 4) AS PREVIOUSLY REQUESTED PROVIDE ENGINEERING FOR | | | ANCHORING THE EQUIPMENT TO RESIST WIND PRESSURES. | | | ENGINEERING FROM THE MANUFACTURER IS ACCEPTABLE IF THE | | | DESIGN CRITERIA IS COMPLIANTT WITH SECTION R301.2.1 | | | FBC-14 RESIDENTIAL. | | | | | | 5) PROVIDE THE CLEARANCE DISTANCE FROM THE TOWER TO THE | | | BUILDING. | | | | | | 6) INDICATE HOW THE HEAT PUMPS IN THE GARAGE WILL BE | | | PROTECTED FROM VEHICULAR DAMAGE | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|