2016-06-23 09:39:302ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15091310
 6/23/16
  
 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PROVIDE
 AHRI CERTIFICATES FOR THE HEAT PUMPS, SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE HEAT PUMPS AND
 COOLING TOWER, AND PROVIDE STRUCTURAL DETAILS FOR
 INSTALLATION OF THE COOLING TOWER CONCRETE MOUNTING
 PAD, AND WIND LOAD ENGINEERING FOR ANCHORING THE TOWER
 TO THE PAD. PLEASE NOTE THAT THE PLAN SHOWS A PAD FOR
 THE THE TOWER, HOWEVER THE SURVEY INDICATES AN EXISTING
 CONCRETE DECK. PLEASE CLARIFY WHICH IS APPLICABLE TO
 THE PROJECT.
  
 2) SHEET M-1: THE PLAN IS SPECIFYING BOTH FLORIDA HEAT
 PUMPS (AC-1 & 2), AND TRANE AHU'S 1 & 2: PLEASE CLARIFY
 WHICH UNITS WILL BE INSTALLED.
  
 3) M-1: PROVIDE WATER PIPING SPECIFICATIONS AND THE
 TYPE, SIZE AND THICKNESS OF THE PIPING INSULATION.
 CLARIFY HOW THE PIPING WILL BE RUN FROM THE COOLING
 TOWER TO THE BUILDING AND HOW IT WILL BE PROTECTED .
 INCLUDE THE PIPING AND INSULATUION DATA IN THE ENERGY
 CALCULATIONS.
  
 4) THE ENERGY CALCULATION FORM R406-2014 MUST BE SIGNED
 AND DATED BY THE OWNER/AGENT SUBMITTED, AND MUST ALSO
 BEAR THE ORIGINAL SIGNATURE OF THE PREPARER.
  
 5) M-1: PLEASE ADD THE 4X2 SUPPLY GRILLS TO THE LEGEND
  
 6) PROVIDE DETAILS FOR THE WATER SOURCE TO THE COOLING
 TOWER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER