| 2015-12-15 14:16:06 | 3RD REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL |
| | |
| | PROVISIONALLY APPROVED: |
| | |
| | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO |
| | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 |
| | FEET OF EACH SLEEPING ROOM. |
| | NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME |
| | POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET |
| | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. |
| | FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| | BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER |
| | INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. |
| | FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES. |
| | IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE LISTED |
| | TAMPER-RESISTANT RECEPTACLES. |
| | (2) WALL SPACE. AS USED IN THIS SECTION, A WALL SPACE |
| | SHALL |
| | INCLUDE THE FOLLOWING: |
| | (1) ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING |
| | SPACE MEASURED AROUND CORNERS) AND UNBROKEN ALONG |
| | THE FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS, |
| | FIREPLACES, |
| | AND FIXED CABINETS |
| | (2) THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR |
| | WALLS, |
| | EXCLUDING SLIDING PANELS |
| | (3) THE SPACE AFFORDED BY FIXED ROOM DIVIDERS, SUCH AS |
| | FREESTANDING BAR-TYPE COUNTERS OR RAILINGS |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | CHIEF PLANS EXAMINER |