| 2015-10-08 16:21:07 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15091275 |
| | ADD: 4375 EASLEY DR. |
| | CONT: FLORIDA DESIGN DRILLING CORP. |
| | TEL: (561)844-2966 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. OCT. 08/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S4.1 INDICATES THIE OCCUPANCY TO BE A UTILITY |
| | OCCUPANCY (BARNS, CARPORTS, GREEN HOUSES ETC) VERSES A |
| | F3 OCCUPANCY, BUILDINGS DESIGNED FOR PICTICULAR TYPES |
| | OF OPERATIONS, CHARACTERIZED BY A RELATIVELY LOW DESITY |
| | OF EMPLOYEEPOPULATION WITH MUCH OF THE AREA OCCUPIED BY |
| | MACHINERY OR EQUIPMENT, STEEL MILLS, GENERATING PLANTS, |
| | WATER TREATMENT PLANTS ... |
| | |
| | 2) SHEET S4.1 PROVIDES THE WIND DESIGN CRITERIA, 180 |
| | VULT MPH, EXPOSURE C, |
| | 2A) MISSING APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | 2B) MISSING COMPONENTS & CLADDING PRESSURES 2014 FBC-B |
| | 1603.1.4 WIND DESIGN DATA. |
| | |
| | 3) PLEASE CONVERT VULT INTO VASD PRESSURES SINCE ALL OF |
| | THE PRODUCT APPROVALS ARE IN VASD. |
| | |
| | 4) PLEASE SUBMIT PRODUCT APPROVALS FOR REVIEW FOR CODE |
| | COMPLIANCE, SUBMIT (2) SETS OF EACH APPROVAL. 107.1. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C), WALL LOUVERS |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) SHEET S2.2 INDICATES THE USE OF THESE PRODUCTS |
| | SIKATOP 122, SIKA ARMATER 110 EPOCEM BOND AGENT & |
| | SIKATOP 123 PLUS, PLEASE SUBMIT 2 COPIES OF THE |
| | MANUFACTURERS SPEC/ INSTALATION GUIDE. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |