| Notes |
| Date |
Text |
| 2015-10-08 13:54:52 | 1ST REVIEW: FBC 2014 MECHANICAL | | | | | | 1) REFER TO SECTION 601.2: AIR MOVEMENT IN EGRESS | | | ELEMENTS. | | | CORRIDORS SHALL NOT SERVE AS SUPPLY, RETURN, EXHAUST, | | | RELIEF OR VENTILATION AIR DUCTS. | | | PLEASE REVISE THE LAYOUT PLAN TO SHOW COMPLIANCE. | | | 2) DUCT SMOKE DETECTORS ARE SHOWN IN THE RETURN AIR | | | PLENUMS: REFER TO SECTION 606.4 CONTROLS OPERATION, AND | | | 606.4.1 SUOERVISION, AND PROVIDE DETAILS INDICATING | | | COMPLIANCE. PLEASE CLARIFY IF BOTH SYSTEMS WILL SHUT | | | DOWN SIMULTANEOUSLY IF ONLY ONE SYSTEM DETECTOR | | | ACTIVATES. | | | 3) PROVIDE WIND LOAD ENGINEERED TIE-DOWN DETAILS FOR | | | ANCHORING THE AC CONDENSERS- SECTION 301.15 FBC-14 | | | MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|