| Plan Review Notes For Permit 15091246 |
| Permit Number |
15091246 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-04 05:53:55 | 1) SHOW THE DIMENSIONS OF THE AREA OF THE SLAB TO BE | | | REMOVED AND SUBMIT A SLAB REPAIR DETAIL SHOWING HOW THE | | | THE STRUCTURAL INTEGRITY OF THE SLAB WILL BE | | | MAINTAINED. SHOW THE SIZE OF DOWELS, SPACING OF DOWELS, | | | EMBEDMENT DEPTH INTO EXISTING SLAB AND NEW SLAB AND HOW | | | SECURED INTO EXISTING SLAB. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 2) THE SOIL SHALL BE POISONED FOR TERMITES PRIOR TO | | | PLACEMENT OF CONCRETE AND TERMITE CERTIFICIATE SHALL BE | | | ON JOBSITE. | | | 3) SHOW THE REQUIRED VAPOR BARRIER ON THE SLAB REPAIR | | | DETAIL & AND PSI OF CONCRETE. COMPLY WITH FBC | | | SEC.1816,1907. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|