| 2015-11-02 18:05:15 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE ARCHITECTURAL AND STRUCTURAL PLANS HAVE SEVERAL |
| | REFERENCES TO THE 2010 FBC. THE FBC FIFTH EDITION |
| | (2014) WENT INTO EFFECT ON JUNE 30, 2015. ALL NEW |
| | PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED |
| | TO COMPLY WITH AND REFERENCE THE FBC FIFTH EDITION. |
| | |
| | 2) SUBMIT A SURVEY THAT SHOWS THE PROPOSED STRUCTURE ON |
| | THE SUB-DIVIDED LOT. (TWO REQUIRED) FBC 107.2.1 |
| | |
| | 3) THE ATTIC ACCESS SECTION ON SHEET A-1 SHOWS R-19 |
| | INSULATION ON THE CEILING. THIS DOES NOT CORRESPOND |
| | WITH THE NON-VENTED ATTIC WITH SPRAY FOAM INSULATION |
| | UNDER THE ROOF DECK SHOWN ON THE BUILDING AND WALL |
| | SECTIONS. FBC 107.2.1 |
| | |
| | 4) THE NOTE FOR EGRESS WINDOWS AND SHEET A-1 |
| | INCORRECTLY STATES THAT SLEEPING ROOMS ARE REQUIRED TO |
| | HAVE A MINIMUM TOTAL GLASS AREA OF 5.0 SQUARE FEET ON |
| | THE GROUND FLOOR. THIS SHOULD STATE " THE MINIMUM NET |
| | CLEAR OPENING" , NOT " MINIMUM TOTAL GLASS AREA". |
| | FBC-R310.1.1 |
| | |
| | 5) FBC-R807.1 REQUIRES ATTIC ACCESS OPENINGS TO BE A |
| | MINIMUM OF 22" X 30". THE ATTIC ACCESS ON A-1 IS |
| | SPECIFIED AS 22" X 22". |
| | |
| | 6) SPECIFY THE MEAN ROOF HEIGHT AND PROVIDE THE WIND |
| | DESIGN DATA ON THE STRUCTURAL PLANS.FBC-R 301.2.1 |
| | |
| | 7) SPECIFY THE COMPONENT AND CLADDING PRESSURES ON THE |
| | STRUCTURAL PLANS. FBC-R 301.2.1 |
| | |
| | 8) THERE ARE STRUCTURAL DETAILS AND TABLES ON PLAN |
| | SHEETS A-2, A-3 AND A-4. THE STRUCTURAL ENGINEER IS |
| | REQUIRED TO SIGN AND SEAL ALL OF THE PLANS THAT CONTAIN |
| | STRUCTURAL INFORMATION. FS 471.025 |
| | |
| | 9) THE WIND LOAD PRESSURES FOR THE SINGLE IN-SWING AND |
| | OUT-SWING DOORS AT THE LOGGIA AND WINDOW (K) ARE NOT |
| | SPECIFIED ON THE PLANS. FBC107.2.1 |
| | |
| | 10) A SEPARATE PERMIT, APPLICATION AND REVIEWS ARE |
| | REQUIRED FOR THE GAS GENERATOR, LANDSCAPING, DRIVEWAY |
| | AND SWIMMING POOL. |
| | |
| | |