| 2016-01-25 10:40:45 | RESIDENTIAL (R3) ADDITION, THIRD MECHANICAL REVIEW |
| | CHECKLIST. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS USING |
| | APPROVED SOFTWARE AS REQUIRED BY SEC. R403.6.1 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT |
| | COMMENT). |
| | RESPONSE: NO INFORMATION WAS SUBMITTED. |
| | |
| | 2- SHEET M-1: |
| | A) PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE |
| | BALANCED RETURN AIR FOR THE MASTER BEDROOM AS REQUIRED |
| | BY SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | RESPONSE: 10" TRANSFER DUCT SIZE AS SHOWN ON A/C PLAN |
| | DOESN'T COMPLY. NEED 13" DUCT SIZE OR LARGER. (REPEAT |
| | COMMENT). |
| | |
| | B) INFORMATION ON THE CONDENSING UNIT MOUNTING DETAIL |
| | DOESN'T MATCH INFORMATION SHOWN ON THE FLORIDA PRODUCT |
| | APPROVAL FL14239-R3 SUBMITTED. REVISE AS REQUIRED TO |
| | MATCH. CLEARLY IDENTIFY SIZE, NUMBER AND LOCATION OF |
| | ANCHORS. SEE PRODUCT APPROVAL SUBMITTED. SEC. 107.2.1 |
| | CITY AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY |
| | INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS. |
| | DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD |
| | DRAWINGS FOR REFERENCE. |
| | |