Plan Review Notes
Plan Review Notes For Permit 15091231
Permit Number 15091231
Review Stop M
Sequence Number 3
Notes
Date Text
2016-01-25 10:40:45RESIDENTIAL (R3) ADDITION, THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS USING
 APPROVED SOFTWARE AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
 RESPONSE: NO INFORMATION WAS SUBMITTED.
  
 2- SHEET M-1:
 A) PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE
 BALANCED RETURN AIR FOR THE MASTER BEDROOM AS REQUIRED
 BY SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: 10" TRANSFER DUCT SIZE AS SHOWN ON A/C PLAN
 DOESN'T COMPLY. NEED 13" DUCT SIZE OR LARGER. (REPEAT
 COMMENT).
  
 B) INFORMATION ON THE CONDENSING UNIT MOUNTING DETAIL
 DOESN'T MATCH INFORMATION SHOWN ON THE FLORIDA PRODUCT
 APPROVAL FL14239-R3 SUBMITTED. REVISE AS REQUIRED TO
 MATCH. CLEARLY IDENTIFY SIZE, NUMBER AND LOCATION OF
 ANCHORS. SEE PRODUCT APPROVAL SUBMITTED. SEC. 107.2.1
 CITY AMENDMENTS. (REPEAT COMMENT. NOT ADDRESSED).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY
 INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS.
 DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved