2016-01-22 17:52:48RESIDENTIAL (R3) ADDITION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) GARAGE DOOR THAT MEETS THE ENGINEER OF RECORD
 CALCULATED DESIGN PRESSURES. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: GARAGE OVERHEAD DOOR SHOWN ON FLORIDA PRODUCT
 APPROVAL FL5678-R3 SUBMITTED DOESN'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD. (REPEAT
 COMMENT).
  
 2- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT APPROVAL
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- REVISE THE ENERGY CALCULATIONS SUBMITTED:
 A) THE CEILING INFORMATION SHOWN ON ITEM #10 DOESN'T
 MATCH PLANS. PLANS CALL FOR AN UNVENTED ATTIC NOT
 VENTED. SEE PLANS AND REVISE AS REQUIRED. SEC. R103.2
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) REVISE CLIMATE ZONE ON PAGE 2 OF 5. SEE CLIMATE
 ZONES ON TABLE C301.1 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014) AND REVISE AS REQUIRED.
  
 C) REVISE ROOF TYPE ON PAGE 2 OF 5 TO MATCH PLANS.
 PLANS SHOW GABLE ROOF NOT HIP. SEE PLANS AND REVISE ASS
 REQUIRED. SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 D) REVISE DOOR TYPE SHOWN ON PAGE 3 OF 5. PLANS AND
 PRODUCT APPROVAL SUBMITTED DON'T SHOW ANY WOOD DOORS.
 PRODUCT APPROVAL SUBMITTED IS FOR ALUMINUM GLAZED
 DOORS. THESE DOORS NEED TO BE INCLUDED IN THE WINDOWS
 SEC. AS REQUIRED BY SEC. R405.5.3.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 E) THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 NEEDS TO BE COMPLETED BY THE BUILDER AS REQUIRED BY
 SEC. R405.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 F) THE AIR BARRIER AND INSULATION INSPECTION COMPONENT
 CRITERIA NEEDS TO BE COMPLETED AS REQUIRED BY SEC.
 R405.4.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING
 BUILDER'S NAME, PERMITTING OFFICE AND JURISDICTION
 NUMBER. SEC. R101.5.1.1.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 NOTE: PROVIDE THE CORRECT NAME OF THE BUILDER. THIS IS
 NOT AN OWNER/BUILDER CONSTRUCTION.
  
 H) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION
 SHOWN ON PAGE 3 OF 4 TO MATCH PLANS. SEC. R405.5.3.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE DEFAULT FACTOR FOR GLAZING.
  
 4- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. PLANS TO SHOW THE MINIMUM SIZE OF CEILING FAN
 AS REQUIRED BY TABLE R405.7.6 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY
 INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS.
 DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  