2015-12-10 13:54:38RESIDENTIAL (R3) ADDITION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
  
 ****NOTE:
 THERE ARE TWO OPTIONS TO ADDRESS COMMENTS BELOW. PERMIT
 MAY BE ISSUED WITH PROVISO OR CONTRACTOR MAY RE-SUBMIT
 INFORMATION ADDRESSING THE COMMENTS. PROVISO MEANS THAT
 CONTRACTOR WILL ADDRESS ALL THE COMMENTS AFTER THE
 PERMIT IS ISSUED. REVISION FEES WILL APPLY. CONTRACTOR
 TO ADVICE PREFERRED OPTION: PROVISO OR RE-SUBMITTAL.
  
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS USING
 APPROVED SOFTWARE AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
 RESPONSE: COMPLETE EQUIPMENT SIZING CALCULATIONS WERE
 NOT SUBMITTED.
  
 2- SHEET M-1:
 A) PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE
 BALANCED RETURN AIR FOR THE MASTER BEDROOM AS REQUIRED
 BY SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE: 10" TRANSFER DUCT SIZE AS SHOWN ON A/C PLAN
 DOESN'T COMPLY. NEED 13" DUCT SIZE OR LARGER.
  
 B) INFORMATION ON THE CONDENSING UNIT MOUNTING DETAIL
 DOESN'T MATCH INFORMATION SHOWN ON THE FLORIDA PRODUCT
 APPROVAL FL14239-R3 SUBMITTED. REVISE AS REQUIRED TO
 MATCH. CLEARLY IDENTIFY SIZE, NUMBER AND LOCATION OF
 ANCHORS. SEE PRODUCT APPROVAL SUBMITTED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY
 INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS.
 DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  