| 2015-12-10 19:00:19 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6700 |
| | [email protected] |
| | ALTERNATE CONTACT |
| | PHIL PETTY |
| | 561-805-6742 |
| | [email protected] |
| | |
| | |
| | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE |
| | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE |
| | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON |
| | FLOOR PLAN. |
| | |
| | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. |
| | FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| | BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER |
| | INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. |
| | |
| | C402.4.8 RECESSED LIGHTING. |
| | RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| | ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED |
| | LUMINAIRES SHALL BE IC-RATED AND LABELED AS HAVING AN |
| | AIR LEAKAGE RATE OF NOT MORE THAN 2.0 CFM (0.944 L/S) |
| | WHEN TESTED IN ACCORDANCE WITH ASTM E 283 AT A 1.57 PSF |
| | (75 PA) PRESSURE DIFFERENTIAL. ALL RECESSED LUMINAIRES |
| | SHALL BE SEALED WITH A GASKET OR CAULK BETWEEN THE |
| | HOUSING AND INTERIOR WALL OR CEILING COVERING. |
| | 75 % LAMPS MUST BE HIGH EFFCIENCY. |
| | |
| | GENERAL NOTE # 5 SHOWS THHN INSULATION HOWEVER NOT |
| | RATED FOR WET LOCATION NEED TO SHOW THWN / COMBINATION. |
| | W / H DOESN'T SHOW DISCONECTING MEANS WITHIN SIGHT. |
| | |
| | (1) ONE-FAMILY AND TWO-FAMILY DWELLINGS. FOR A |
| | ONEFAMILY |
| | DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT |
| | IS AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET |
| | ACCESSIBLE |
| | WHILE STANDING AT GRADE LEVEL AND LOCATED NOT MORE THAN |
| | 2.0 M (61?2 FT) ABOVE GRADE SHALL BE INSTALLED AT THE |
| | FRONT AND BACK OF THE DWELLING. |
| | |
| | PROVIDE GFCI PROTECTION IN GARAGE , OUTDOORS , AND IN |
| | LAUNDRY ROOM. |
| 2015-12-10 13:48:06 | NEW DRAWINGS SUBMITTED. JG. |