Plan Review Notes
Plan Review Notes For Permit 15091231
Permit Number 15091231
Review Stop E
Sequence Number 2
Notes
Date Text
2015-12-10 19:00:191ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 C402.4.8 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND LABELED AS HAVING AN
 AIR LEAKAGE RATE OF NOT MORE THAN 2.0 CFM (0.944 L/S)
 WHEN TESTED IN ACCORDANCE WITH ASTM E 283 AT A 1.57 PSF
 (75 PA) PRESSURE DIFFERENTIAL. ALL RECESSED LUMINAIRES
 SHALL BE SEALED WITH A GASKET OR CAULK BETWEEN THE
 HOUSING AND INTERIOR WALL OR CEILING COVERING.
 75 % LAMPS MUST BE HIGH EFFCIENCY.
  
 GENERAL NOTE # 5 SHOWS THHN INSULATION HOWEVER NOT
 RATED FOR WET LOCATION NEED TO SHOW THWN / COMBINATION.
 W / H DOESN'T SHOW DISCONECTING MEANS WITHIN SIGHT.
  
 (1) ONE-FAMILY AND TWO-FAMILY DWELLINGS. FOR A
 ONEFAMILY
 DWELLING AND EACH UNIT OF A TWO-FAMILY DWELLING THAT
 IS AT GRADE LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE
 WHILE STANDING AT GRADE LEVEL AND LOCATED NOT MORE THAN
 2.0 M (61?2 FT) ABOVE GRADE SHALL BE INSTALLED AT THE
 FRONT AND BACK OF THE DWELLING.
  
 PROVIDE GFCI PROTECTION IN GARAGE , OUTDOORS , AND IN
 LAUNDRY ROOM.
2015-12-10 13:48:06NEW DRAWINGS SUBMITTED. JG.