| 2015-12-09 16:59:11 | RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | ****NOTE: |
| | THERE ARE TWO OPTIONS TO ADDRESS COMMENTS BELOW. PERMIT |
| | MAY BE ISSUED WITH PROVISO OR CONTRACTOR MAY RE-SUBMIT |
| | INFORMATION ADDRESSING THE COMMENTS. PROVISO MEANS THAT |
| | CONTRACTOR WILL ADDRESS ALL THE COMMENTS AFTER THE |
| | PERMIT IS ISSUED. REVISION FEES WILL APPLY. CONTRACTOR |
| | TO ADVICE PREFERRED OPTION: PROVISO OR RE-SUBMITTAL. |
| | |
| | 1- GARAGE DOOR LEADING TO THE INTERIOR OF THE HOUSE: |
| | PROVIDE SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. |
| | R302.5.1 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | SPECIFY FIRE RATED DOOR AND SELF CLOSING. |
| | RESPONSE: THERE ARE NOT SPECIFICATIONS FOR SELF-CLOSING |
| | DOOR. |
| | |
| | 2- DETAIL 4/S-2: SPECIFY SPACING FOR THE #5 REBAR AT |
| | EXISTING PARAPET EXTENSION. SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | RESPONSE: SPACING OF #5 REBARS WAS NOT SPECIFIED. |
| | |
| | 3- TYPICAL STEM WALL SECTION ON SHEET S-2: |
| | A) PROVIDE ICYNENE ICC EVALUATION REPORT. (2 COPIES). |
| | ICC REPORT TO BE REVIEWED AND APPROVED BY THE ENGINEER |
| | OF RECORD PRIOR TO SUBMITTAL TO THIS OFFICE. SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | RESPONSE: ICC EVALUATION REPORT SUBMITTED EXPIRED ON |
| | FEBRUARY 1, 2015, PROVIDE CURRENT REPORT. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) GARAGE DOOR THAT MEETS THE ENGINEER OF RECORD |
| | CALCULATED DESIGN PRESSURES. SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | RESPONSE: NO PRODUCT APPROVAL SUBMITTED. |
| | |
| | 5- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT APPROVAL |
| | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 6- REVISE THE ENERGY CALCULATIONS SUBMITTED: |
| | A) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING |
| | BUILDER'S NAME AND PERMITTING OFFICE. SEC. R101.5.1.1.2 |
| | OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT |
| | COMMENT). |
| | |
| | B) OWNER/AGENT TO PROPERLY SIGN AND DATE BOTTOM OF |
| | FORM. THE FORM SUBMITTED WAS NOT SIGNED BY THE OWNER. |
| | IT ONLY STATES "TIESHA & RONALD SMALL". THIS IS NOT A |
| | SIGNATURE. R103.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). (REPEAT COMMENT). |
| | |
| | C) REVISE THE DOORS INFORMATION ON PAGE 3 OF 4. THERE |
| | IS NOT INSULATED WOOD DOOR ON THE WEST ELEVATION. THIS |
| | DOOR NEEDS TO BE CONSIDERED AS GLAZING AS REQUIRED BY |
| | SEC. R405.5.3.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). SEE PRODUCT APPROVAL SUBMITTED. (REPEAT |
| | COMMENT). |
| | |
| | D) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION |
| | SHOWN ON PAGE 3 OF 4 TO MATCH PLANS. SEC. R405.5.3.2 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT |
| | COMMENT). NOTE: ALSO, COORDINATE GLAZING AREA WITH ITEM |
| | #6(C) ABOVE. (REPEAT COMMENT). |
| | |
| | E) THE BUILDER NEEDS TO COMPLETE AND SIGN/DATE THE |
| | BOTTOM OF THE ENERGY PERFORMANCE LEVEL CARD (EPL). SEC. |
| | R405.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | F) CLIMATE ZONE SHOWN ON PAGE 2 OF 5 IS INCORRECT. SEE |
| | TABLE R301.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014) AND REVISE. |
| | |
| | G) INSULATION R-VALUE SHOWN ON ITEM #10 IS INCORRECT. |
| | SEE PLANS AND REVISE AS REQUIRED. SEC. R103.2 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | H) REVISE R-VALUE ON CEILING INFORMATION ON PAGE 2 OF |
| | 5. SEE PLANS AND REVISE AS REQUIRED. SEC. R103.2 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR |
| | AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS |
| | WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING |
| | THE DEFAULT FACTOR FOR GLAZING. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY |
| | INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS. |
| | DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD |
| | DRAWINGS FOR REFERENCE. |
| | |