2015-10-30 18:32:52RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS USING APPROVED
 SOFTWARE AS REQUIRED BY SEC. R403.6.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). CALCULATIONS
 SUBMITTED ARE NOT FROM AN APPROVED SOFTWARE. SEE ACCA
 WEBSITE FOR APPROVED SOFTWARE.
  
 2- SHEET M-1:
 A) PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE
 BALANCED RETURN AIR FOR THE MASTER BEDROOM AS REQUIRED
 BY SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) UPDATE CODE REFERENCED ON THE MECHANICAL NOTES.
 CURRENT CODE IS FBC- 5TH EDITION (2014).
  
 C) CONDENSING UNIT MOUNTING DETAIL SUBMITTED: PROVIDE
 ENGINEERING CALCULATIONS SHOWING THAT NUMBER AND SIZE
 OF ANCHORS SPECIFIED WILL RESIST THE CALCULATED WIND
 LOADS. AND, CLEARLY IDENTIFY LOCATION OF ANCHORS. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY
 INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS.
 DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  