| 2015-10-30 18:32:52 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS USING APPROVED |
| | SOFTWARE AS REQUIRED BY SEC. R403.6.1 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). CALCULATIONS |
| | SUBMITTED ARE NOT FROM AN APPROVED SOFTWARE. SEE ACCA |
| | WEBSITE FOR APPROVED SOFTWARE. |
| | |
| | 2- SHEET M-1: |
| | A) PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE |
| | BALANCED RETURN AIR FOR THE MASTER BEDROOM AS REQUIRED |
| | BY SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) UPDATE CODE REFERENCED ON THE MECHANICAL NOTES. |
| | CURRENT CODE IS FBC- 5TH EDITION (2014). |
| | |
| | C) CONDENSING UNIT MOUNTING DETAIL SUBMITTED: PROVIDE |
| | ENGINEERING CALCULATIONS SHOWING THAT NUMBER AND SIZE |
| | OF ANCHORS SPECIFIED WILL RESIST THE CALCULATED WIND |
| | LOADS. AND, CLEARLY IDENTIFY LOCATION OF ANCHORS. SEC. |
| | 107.2.1.3 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY |
| | INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS. |
| | DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD |
| | DRAWINGS FOR REFERENCE. |
| | |