2015-10-29 15:17:39RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- WINDOWS ON THE NORTH WALL OF EXISTING BEDROOMS #1
 AND #2 ARE GOING TO BE BLOCKED TO ALLOW FOR THE NEW
 ADDITION. EGRESS IS GOING TO BE REDUCED. SPECIFY AT
 LEAST ONE WINDOW TYPE AND SIZE FOR EACH BEDROOM THAT
 WILL COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. R310
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- SIZE OF NEW ENTRY DOOR NEEDS TO COMPLY WITH SEC.
 R311.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014). THE DOOR
 LEAF SHALL PROVIDE A MINIMUM CLEAR WIDTH OF 32". PAIR
 OF 5'-0" X 6'-8" FRENCH DOORS SPECIFIED PROVIDES 2'-6"
 LEAF DOOR WHICH DOESN'T ALLOW 32" CLEAR OPENING. REVISE
 SIZE OF DOORS AS REQUIRED.
  
 4- GARAGE DOOR LEADING TO THE INTERIOR OF THE HOUSE:
 PROVIDE SPECIFICATIONS SHOWING COMPLIANCE WITH SEC.
 R302.5.1 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 SPECIFY FIRE RATED DOOR AND SELF CLOSING.
  
 5- SPECIFY CARBON MONOXIDE ALARMS BY EXISTING BEDROOMS
 AS REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 6- A) SPECIFY ATTIC ACCESS SIZE. ALSO, LOCATION OF
 ATTIC ACCESS TO COMPLY WITH SEC. R807 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). CHECK FOR HEIGHT
 CLEARANCE.
  
 B) DESIGN PARAMETERS ON SHEET S-3: SPECIFY THE ATTIC
 LIVE LOAD AS REQUIRED BY TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). CLEARLY SPECIFY IF
 DESIGNING ATTIC WITH OR WITHOUT STORAGE. SEE GENERAL
 ROOF NOTE #13 AND FOOTNOTES ON TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 7- DETAIL 4/S-2: SPECIFY SPACING FOR THE #5 REBAR AT
 EXISTING PARAPET EXTENSION. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 8- TYPICAL STEM WALL SECTION ON SHEET S-2:
 A) LOCATION OF FOAM ICYNENE INSULATION SHOWN ON THE
 TYPICAL WALL IS INCORRECT. ICYNENE FOAM INSULATION IS
 USED TO ENCLOSE THE BUILDING THERMAL ENVELOPE AT THE
 UNDERSIDE OF THE ROOF SHEATHING SO ATTIC VENTILATION IS
 NOT REQUIRED. REVISE AS REQUIRED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014)
  
 B) PROVIDE ICYNENE ICC EVALUATION REPORT. (2 COPIES).
 ICC REPORT TO BE REVIEWED AND APPROVED BY THE ENGINEER
 OF RECORD PRIOR TO SUBMITTAL TO THIS OFFICE. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 C) CLARIFY IF ENGINEER IS DESIGNING AN UNVENTED ATTIC
 OR VENTED ATTIC. WALL SECTIONS CALL FOR ICYNENE FOAM
 INSULATION AND THERE ARE ALSO SPECIFICATIONS FOR 7" X
 24" SCREEN VENTS AT 8'-0" O.C. SEC. R806 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 9- TYPICAL WOOD BUCK TO CONCRETE CONNECTION DETAIL ON
 SHEET S-2:
 A) GARAGE DOOR PROPOSED COLUMNS ARE CONCRETE BLOCK
 FILLED CELLS NOT CONCRETE COLUMNS. IT MAKES A
 SIGNIFICANT STRUCTURAL DIFFERENCE. REVISE DETAIL
 LABELING AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) ENGINEER TO SPECIFY THE GARAGE DOOR CALCULATED
 DESIGN PRESSURES. SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 C) ENGINEER TO PROVIDE CALCULATIONS SHOWING THAT
 PROPOSED ANCHOR SPACING (30"O.C.) SPECIFIED FOR THE
 GARAGE DOOR STRUCTURAL BUCK DETAIL IS ADEQUATE TO
 RESIST THE CALCULATED DESIGN PRESSURES. SEC. 107.2.1.3
 CITY AMENDMENTS. NOTE: THE ATTACHMENT OF THE STRUCTURAL
 GARAGE BUCK IS THE DESIGNER OF RECORD RESPONSIBILITY
 NOT THE GARAGE DOOR PRODUCT APPROVAL. COORDINATE WITH
 GARAGE DOOR PRODUCT APPROVAL TO AVOID CONFLICTS.
  
 10- REVISE ROOF SHEATHING NAILING SPACING SHOWN ON THE
 COMPONENT AND CLADDING PRESSURES ZONES ON SHEET S-4 FOR
 ROOF ZONE 1 AND 2. NEED 6" O.C. NAIL SPACING NOT 12"
 O.C. AS REQUIRED BY SEC. R803.2.3.1 OF FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $80,000. THE
 PERMIT FEE BALANCE IS $1977.58.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ASPHALT SHINGLES. FLORIDA PRODUCT APPROVAL FL9792-R4
 SUBMITTED IS FOR 2010 FBC. NEED FLORIDA PRODUCT
 APPROVAL FOR THE CURRENT CODE IN EFFECT , 2014 CODE
 VERSION
  
 B) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL239-R17 SUBMITTED IS FOR 2010 FBC. NEED FLORIDA
 PRODUCT APPROVAL FOR THE CURRENT CODE IN EFFECT , 2014
 CODE VERSION
  
 C) GARAGE DOOR THAT MEETS THE ENGINEER OF RECORD
 CALCULATED DESIGN PRESSURES. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 D) FRENCH DOORS IN NEW ENTRY. FLORIDA PRODUCT APPROVAL
 FL253-R11 SUBMITTED IS FOR 2010 FBC. NEED FLORIDA
 PRODUCT APPROVAL FOR THE CURRENT CODE IN EFFECT , 2014
 CODE VERSION
  
 E) WINDOW MULLIONS. AND CLEARLY MARK SIZE OF MULLION
 USED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF
 SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 13- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 14-REVISE THE ENERGY CALCULATIONS SUBMITTED (NOTE:
 COORDINATE WITH PLANS TO AVOID CONFLICTS/DELAYS):
 A) ADDRESS ON TOP FORM IS INCORRECT. ALSO, COMPLETE ALL
 THE INFORMATION ON TOP OF FORM, INCLUDING BUILDER'S
 NAME, PERMIT OFFICE AND JURISDICTION NUMBER. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) COORDINATE CEILING INFORMATION ON ITEM #10 WITH
 PLANS. PLANS NEED TO BE REVISED. THEY SHOW CONFLICTING
 INFORMATION: VENTED AND UNVENTED ATTICS. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) OWNER/AGENT TO PROPERLY SIGN AND DATE BOTTOM OF
 FORM. THE FORM SUBMITTED WAS NOT SIGNED BY THE OWNER.
 IT ONLY STATES "SMALL'S RESIDENCE". IDENTIFY WHO
 CERTIFIES AS OWNER/AGENT AS REQUIRED BY SEC. R103.1.1.2
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) REVISE "SPACES" INFORMATION ON PAGE 2 OF 4. THERE IS
 NOT KITCHEN IN THIS ADDITION. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) REVISE THE ROOF TYPE SHOWN ON PAGE 2 OF 4. THIS IS A
 GABLE TYPE OF ROOF NOT HIP. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) REVISE THE DOORS INFORMATION ON PAGE 3 OF 4. THERE
 IS NOT INSULATED DOOR ON THE WEST ELEVATION. THIS DOOR
 NEEDS TO BE CONSIDERED AS GLAZING AS REQUIRED BY SEC.
 R405.5.3.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). SEE PRODUCT APPROVAL SUBMITTED.
  
 G) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION
 SHOWN ON PAGE 3 OF 4 TO MATCH PLANS. SEC. R405.5.3.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE PUT TOGETHER TWO NEW SET OF DRAWINGS BY
 INSERTING REVISED DRAWINGS AND REMOVING OLD DRAWINGS.
 DON'T STAPLE OLD DRAWINGS TO NEW SET.. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  