Plan Review Notes
Plan Review Notes For Permit 15091225
Permit Number 15091225
Review Stop P
Sequence Number 3
Notes
Date Text
2016-01-23 07:39:421) SHT. A102 - SHOW THE REQUIRED CLEAR FLOOR SPACE FOR
 THE BREAK ROOM SINK ON THE 2ND LEVEL ON THE PLANS PER
 THE 2014 FBC-ACCESS. SEC. 606.2.IS THE SINK DESIGNED
 FOR A FORWARD OR PARALLEL APPROACH? IF FOR A PARALLEL
 APPROACH, IT APPEARS AS THOUGH THE REFRIGERATOR MAY
 INTERFERE WITH ACCESS TO THE FAUCET CONTROLS BY SOMEONE
 IN A WHEELCHAIR. CLARIFY.
 2) SHT. 120 DETAIL D/3 - THE SHOWER CONTROLS SHALL BE
 LOCATED A MAXIMUM OF 27 INCHES FROM THE SIDE WALL
 BEHIND THE SEAT PER THE 2014 FBC-ACCESS. SEC.608.5.3.
 SHOW THIS ON THE DETAIL.
 3) SHT. P300 - DETAIL #13 - DOWNSPOUTS FOR ROOF
 DRAINAGE SHALL DISCHARGE A MINIMUM OF ONE FOOT FROM THE
 BUILDING WALL PER THE 2014 FBC SEC. 1503.7.
 4) SHT. P201 - SUBMIT NOTES FOR NUMBERS 1-4 SURROUNDED
 BY A HEXAGON. WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  