| Plan Review Notes For Permit 15091225 |
| Permit Number |
15091225 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-01-23 07:39:42 | 1) SHT. A102 - SHOW THE REQUIRED CLEAR FLOOR SPACE FOR | | | THE BREAK ROOM SINK ON THE 2ND LEVEL ON THE PLANS PER | | | THE 2014 FBC-ACCESS. SEC. 606.2.IS THE SINK DESIGNED | | | FOR A FORWARD OR PARALLEL APPROACH? IF FOR A PARALLEL | | | APPROACH, IT APPEARS AS THOUGH THE REFRIGERATOR MAY | | | INTERFERE WITH ACCESS TO THE FAUCET CONTROLS BY SOMEONE | | | IN A WHEELCHAIR. CLARIFY. | | | 2) SHT. 120 DETAIL D/3 - THE SHOWER CONTROLS SHALL BE | | | LOCATED A MAXIMUM OF 27 INCHES FROM THE SIDE WALL | | | BEHIND THE SEAT PER THE 2014 FBC-ACCESS. SEC.608.5.3. | | | SHOW THIS ON THE DETAIL. | | | 3) SHT. P300 - DETAIL #13 - DOWNSPOUTS FOR ROOF | | | DRAINAGE SHALL DISCHARGE A MINIMUM OF ONE FOOT FROM THE | | | BUILDING WALL PER THE 2014 FBC SEC. 1503.7. | | | 4) SHT. P201 - SUBMIT NOTES FOR NUMBERS 1-4 SURROUNDED | | | BY A HEXAGON. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|