Plan Review Notes
Plan Review Notes For Permit 15091225
Permit Number 15091225
Review Stop P
Sequence Number 2
Notes
Date Text
2016-01-05 12:09:482ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.SHEET P201 + P100 HORIZONTAL DRY VENTS ARE NOT
 PERMITTED PER FBC PL SEC 905.3 + 905.4
 DRY VENTS SHALL CONNECT TO HORIZONTAL DRAIN ABOVE THE
 CENTER LINE AT A 45 DEGREE ANGLE OR GREATER AND MUST
 RUN VERTICALLY TO 6IN ABOVE FLOOD LEVEL RIM OF HIGHEST
 FIXTURE.
 (A) THE MOP SINK IN ROOM 132 SHOWS A HORIZONTAL DRY
 VENT.
 (B) THE STAND PIPE FOR THE ELEVATOR SUMP PIT DRAIN
 SHOWS A DRY VENT.
 (C)THE FLOOR DRAIN AND STAND PIPE FOR SPRINKLER DRAIN
 IN ROOM 151 SHOWS A DRY VENT.
  
 2. SHEET P201 + P100 HORIZONTAL DRY VENTS ARE NOT
 PERMITTED PER FBC PL SEC 905.3 + 905.4
 DRY VENTS SHALL CONNECT TO HORIZONTAL DRAIN ABOVE THE
 CENTER LINE AT A 45 DEGREE ANGLE OR GREATER AND MUST
 RUN VERTICALLY TO 6IN ABOVE FLOOD LEVEL RIM OF HIGHEST
 FIXTURE.
 (A)THE MOP SINK AND FLOOR SINK IN PREP KIT ROOM 340
 SHOWS A DRY VENT.
  
 3. SHEET P201 THE 3IN + 2IN VENTS FROM 3RD FL ABOVE
 PREP KIT AREA MUST TIE INTO VENT ABOVE FLOOD LEVEL RIM
 OF FIXTURES ON 4TH FLOOR IT IS SHOWING BEING TIED INTO
 HORIZONTAL DRAIN BELOW 3RD FLOOR. PER FBC PL SEC 905.4
  
 4. PLEASE PROVIDE SPECS FOR DOMESTIC PUMP THAT SHOWS
 THE SPECIFIC STANDARDS THAT THE PUMP MEETS THE SPECS
 THAT ARE PROVIDED DO NOT SHOW SPECIFIC STANDARDS ONLY
 GENERIC ONES. PER WPB AMEND TO FBC SEC107.2.1
  