Plan Review Notes
Plan Review Notes For Permit 15091225
Permit Number 15091225
Review Stop P
Sequence Number 1
Notes
Date Text
2015-10-19 09:19:55 
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.WATER CLOSET SHALL COMPLY WITH FBC ACC. SEC 604.2
 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
 2.GRAB BARS SHALL COMPLY WITH FBC ACC SEC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
 3.SHOWER SEATS SHALL COMPLY WITH FBC SEC 610.3 SHOWER
 COMPARTMENT SEATS.
 WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS,
 AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3
 INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT
 IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND
 SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT
 WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN
 TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE
 BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY
 WITH 610.3.1 OR 610.3.2.
 3.SHOWER CONTROLS SHALL COMPLY WITH FBC ACC. 608.6
 SHOWER SPRAY UNIT AND WATER.
 A SHOWER SPRAY UNIT WITH A HOSE 59 INCHES (1500 MM)
 LONG MINIMUM THAT CAN BE USED BOTH AS A FIXED-POSITION
 SHOWER HEAD AND AS A HAND-HELD SHOWER SHALL BE
 PROVIDED. THE SHOWER SPRAY UNIT SHALL HAVE AN ON/OFF
 CONTROL WITH A NON-POSITIVE SHUT-OFF. IF AN
 ADJUSTABLE-HEIGHT SHOWER HEAD ON A VERTICAL BAR IS
 USED, THE BAR SHALL BE INSTALLED SO AS NOT TO OBSTRUCT
 THE USE OF GRAB BARS. SHOWER SPRAY UNITS SHALL DELIVER
 WATER THAT IS 120?F (49?C) MAXIMUM
 3.PROVIDE SPEC SHEETS ON ELEVATOR SUMP PUMP AND WATER
 HEATERS AND BOOSTERPUMP. PER WPB AMEND TO FBC
 SEC.107.2.1
 4. SHEET P201 PLEASE CLARIFY WHAT IS THE 6IN. STANDPIPE
 FOR SPRINKLER,WHAT IS THIS PIPE BEING USED FOR. WPB
 AMEND TO FBC SEC 107.2.1
 5. SHEET P201 THE 4IN. SOIL STACK THAT IS CONNECTING TO
 THE BUILDING DRAIN IN THE MIDDLE OF THE BATHROOM GROUP
 ON THE FIRST FLOOR IS REQUIRED TO CONNECT DOWN STEAM OF
 THE BATHROOM GROUP. PER FBC P SEC 912.2.1
 6. SHEET P201 THE BREAKROOM SINK P-5 IS NOT VENTED
 SHALL COMPLY WITH FBC P SEC 910.1
 7. PLEASE PROVIDE ISOMETRIC THREE DIMENSIONAL RISER
 DIAGRAMS THE DRAWINGS ON SHEET P201 ARE NOT SUITABLE
 FOR THE PURPOSE OF A COMPREHENSIVE PLAN REVIEW PER WPB
 AMEND.TO FBC SEC 107.2.1
 WHEN NEW DRAWING ARE PROVIDE A COMPLETE PLUMBING REVIEW
 WILL BE DONE THERE MAY BE ADDITIONAL COMMENTS.