2015-11-03 08:48:421ST REVIEW: FBC 2014 MECHANICAL, FBC 2014 ENERGY
 CONSERVATION
 PERMIT #15091225
 11/3/15
  
 1) SHEET A-003: PLEASE ADD THE 2014 (FIFTH EDITION)
 FLORIDA BUILDING CODE- ENERGY CONSERVATION TO THE LIST
 OF APPLICABLE CODES. REFER TO THE FOLLOWING SECTIONS OF
 THE CODE CALLED OUT BELOW AND SHOW COMPLIANCE:
 A ) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION- CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 B) PROVIDE ENERGY CALCULATIONS IN ACORDANCE WITH
 SECTION C101.2 AND C101.5.
 C) REFER TO SECTION C408 SYSTEM COMMISSIONING INCLUSIVE
 OF ALL SUB-SECTIONS AND SUBMIT A COMMISSIONING PLAN.
 PLEASE NOTE THAT PRELIMINARY AND FINAL REPORTS ON THE
 SYSTEMS SHALL BE PROVIDED PER SECTIONS C408.2.4 AND
 C408.2.5.4.
 2) SHEET M101: A) PROVIDE FSD SYMBOLS WHERE THE DUCTS
 ARE PENETRATING THE RATED SHAFT BY THE TOILET ROOMS. B)
 SHOW THE EXACT LOCATIONS OF THE FIRE-RATED ACCESS DOORS
 AT BOTH OF THE RATED SHAFTS, PROVIDE INSTALLATION
 DETAILS, AND A SUBMITTAL FOR THE DOOR REVIEWED AND
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD. C)
 PLEASE PLACE NOTE #7 AT ALL SHAFT DAMPER LOCATIONS: THE
 NOTE IS MSSING IN SEVERAL PLACES.
 3) M101, M102, M103, & M104: REFER TO SECTION 306.1
 ACCESS AND SERVICE SPACE: PROVIDE THE DIMENSIONS OF THE
 VRV ACCESS PANELS AND PROVIDE SECTION CUTS OF THE
 PANELS AND INSTALLATION DETAILS. PLEASE NOTE THAT THE
 CLEAR OPENING DIMENSIONS OF THE PANELS SHALL BE LARGE
 ENOUGH TO REPLACE THE UNITS WITHOUT REMOVING PERMANENT
 CONSTRUCTION.
 4) M300: PROVIDE INSTALLATION AND SUPPORT DETAILS FOR
 THE VRV'S AND EXHAUST FANS, AND DUCT HANGING AND
 CONNECTION DETAILS IN COMPLIANCE WITH THE CURRENT
 SMACNA STANDARDS.
 5) MP100, M300: SITE SPECIFIC WIND LOAD ENGINEERING IS
 REQUIRED FOR INSTALLATION OF THE ROOFTOP HP CONDENSERS,
 THE ERV, THE EXHAUST AND UPBLAST FANS, AND THE GRAVITY
 VENTILATIOR- REFER TO SECTION 301.15 FBC-14 MECHANICAL.
 PLEASE NOTE THAT IN ACCORDANCE WITH THIS SECTION, AND
 SECTIONS 237433 AND 238126 OF THE PROJECT MANUAL, THE
 ERV AND HP CONDENSERS MUST ALSO BE CERTIFIED FOR WIND
 RESISTANCE. PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 DESIGN PRESSURES ON THE PLAN, AND COMPLETE DETAILS FOR
 ATTACHING THE VARIOUS CURBS, STANDS AND SUPPORTS TO THE
 STRUCTURE, AND MOUNTING THE APPLIANCES AND EQUIPMENT TO
 THE SUPPORTS. ALL SUBMITTALS PERTAINING TO THE
 INSTALLATIONS INCLUDING MIAMI-DADE NOA'S, FL, PRODUCT
 APPROVALS, MANUFACTURER'S SPECIFICATIONS ETC. SHALL BE
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD. PROVIDE SECTION CUTS ON THE PLAN THAT INDICATE
 THE HEIGHTS OF THE AC EQUIPMENT ABOVE THE FINISHED
 SURFACES OF THE ROOF- REFER TO TABLE 1522.3 FBC-14
 BUILDING. SEE ALSO SECTION 1522.3.4 FOR ELECTRICAL
 CONDUITS AND MECHANICAL PIPING MOUNTED ON ROOF DECKS
 AND PROVIDE DETAILS.
 6) PROVIDE A SUBMITTAL PACKAGE REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL OF RECORD THAT INCLUDES THE AC
 EQUIPMENT, THE FIRE/SMOKE DAMPERS, THE DUCT SMOKE
 DETECTORS, THE FANS, THE LOUVERS, THE ACCESS DOORS, THE
 MOD'S, REFRIGERANT AND CONDENSATE PIPING INSULATIONS
 (INSULATIONS SHALL BE PLENUM-RATED) ETC. PLEASE NOTE
 MIAMI-DADE NOA'S AND/OR FL. PRODUCT APPROVALS ARE
 REQUIRED FOR ALL EXTERIOR COMPONENTS SUCH AS THE
 EXHAUST FANS AND LOUVERS
 7) PROVIDE UL TESTED AND APPROVED FIRESTOPPING SYSTEMS
 COPIED ONTO THE PLANS FOR ALL PIPES, DUCTS, CONDUITS
 ETC. PENETRATING FIRE-RATED WALLS AND FLOOR/CEILING
 ASSEMBLIES.
 8) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 KITCHEN HOOD AND EXHAUST SYSTEMS.
  