| 2015-10-22 16:33:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1. SHEET 007 A.020, THE EXIT PATH FROM THE WEST DOORS |
| | LEADING THROUGH THE COURTYARD, APPEARS TOO NARROW |
| | INBETWEEN FOR THE OCCUPANCY LOAD. NO DIMENSIONS ARE |
| | INDICATED FOR THE WIDTH BETWEEN THE WATER FOUNTAINS AND |
| | LANDSCAPE. |
| | |
| | 2. SHEET A.605, INDICATES A DOOR SCHEDULE; HOWEVER, A |
| | COLUMN IN THE TABLE REFERENCES A HARDWARE PACKAGE. I |
| | HAVE BEEN UNABLE TO IDENTIFY THE SHEETINDICATING THE |
| | HARDWARE PACKAGE INFORMATION. |
| | |
| | 3. SHEET A-101, INDICATES DOORS 151.1, 152.1 & 132.1, |
| | 132.2 THAT OPEN UP INTO THE EXIT ACCESS WAY. PER NFPA |
| | 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY |
| | OPEN. |
| | |
| | PLEASE PROVIDE FOR COMPLIANCE WITH THE CODE. |
| | |
| | 4. SHEET A-107, F3, INDICATES A 2 PEDESTRIAN SWING |
| | GATES. THERE IS NO INDICATION OF ANY LATCHING OR EXIT |
| | HARDWARE. PER NFPA 101 SECTION 7.2.1.5 THE LOCK/LATCH |
| | RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR |
| | WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| | RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| | OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| | BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| | TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| | TO OPERATE. |
| | |
| | PLEASE PROVIDE FOR COMPLAINCE WITH THE CODE AND FOR |
| | PANIC HARDWARE PER NFPA 101 7.2.1.7. |
| | |
| | 5. FIRE FIGHTER?S EMERGENCY OPERATIONS. |
| | NFPA 101 9.4.3.1 ALL NEW ELEVATORS SHALL CONFORM TO THE |
| | FIRE FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF |
| | ASME A17.1/CSA B44, SAFETY CODE FOR ELEVATORS. |
| | |
| | PLEASE PROVIDE FOR COMPIANCE WITH THE CODE. |
| | |
| | 6. PLEASE PROVIDE DOCUMENTATION THAT THIS BUILDING DOES |
| | NOT MEET THE REQUIRERMENTS OF A HIGH RISE AND THE |
| | REQUIREMENTS PROVISIONS OF NFPA 11.8. |
| | |
| | 7. BASED ON REVIERW OF THE ABOVE ADDITIONAL |
| | REQUIREMENTS MAY BE PROVIDED |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |