Plan Review Notes
Plan Review Notes For Permit 15091225
Permit Number 15091225
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-10-22 16:33:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET 007 A.020, THE EXIT PATH FROM THE WEST DOORS
 LEADING THROUGH THE COURTYARD, APPEARS TOO NARROW
 INBETWEEN FOR THE OCCUPANCY LOAD. NO DIMENSIONS ARE
 INDICATED FOR THE WIDTH BETWEEN THE WATER FOUNTAINS AND
 LANDSCAPE.
  
 2. SHEET A.605, INDICATES A DOOR SCHEDULE; HOWEVER, A
 COLUMN IN THE TABLE REFERENCES A HARDWARE PACKAGE. I
 HAVE BEEN UNABLE TO IDENTIFY THE SHEETINDICATING THE
 HARDWARE PACKAGE INFORMATION.
  
 3. SHEET A-101, INDICATES DOORS 151.1, 152.1 & 132.1,
 132.2 THAT OPEN UP INTO THE EXIT ACCESS WAY. PER NFPA
 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE PROVIDE FOR COMPLIANCE WITH THE CODE.
  
 4. SHEET A-107, F3, INDICATES A 2 PEDESTRIAN SWING
 GATES. THERE IS NO INDICATION OF ANY LATCHING OR EXIT
 HARDWARE. PER NFPA 101 SECTION 7.2.1.5 THE LOCK/LATCH
 RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR
 WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE.
  
 PLEASE PROVIDE FOR COMPLAINCE WITH THE CODE AND FOR
 PANIC HARDWARE PER NFPA 101 7.2.1.7.
  
 5. FIRE FIGHTER?S EMERGENCY OPERATIONS.
 NFPA 101 9.4.3.1 ALL NEW ELEVATORS SHALL CONFORM TO THE
 FIRE FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF
 ASME A17.1/CSA B44, SAFETY CODE FOR ELEVATORS.
  
 PLEASE PROVIDE FOR COMPIANCE WITH THE CODE.
  
 6. PLEASE PROVIDE DOCUMENTATION THAT THIS BUILDING DOES
 NOT MEET THE REQUIRERMENTS OF A HIGH RISE AND THE
 REQUIREMENTS PROVISIONS OF NFPA 11.8.
  
 7. BASED ON REVIERW OF THE ABOVE ADDITIONAL
 REQUIREMENTS MAY BE PROVIDED
  
 PETER LEDUC
 FIRE MARSHAL