Plan Review Notes
Plan Review Notes For Permit 15091225
Permit Number 15091225
Review Stop E
Sequence Number 1
Notes
Date Text
2015-11-23 18:42:58THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 PG. E050
 1. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH ELECTRICAL
 INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN FOR
 INSPECTIONS. NO SITE TUBES WILL BE ACCEPTED.
 2. ALL SITE LIGHTING SHALL BE UNDER SEPARATE PERMIT.
 PG. E201; E202; E203; E204
 1. NEC 314.27(B), BOXES SPECIFICALLY LISTED FOR THE
 APPLICATION SHALL BE USED FOR ALL FLOOR OUTLETS.
 2. NEC 406.9(B), ALL 15 & 20 AMP 125 AND 250 VOLT
 NONLOCKING RECEPTACLES INSTALLED IN WET LOCATIONS SHALL
 BE LISTED WEATHER RESISTANT.
 3. NEC 600.5, EVERY COMMERCIAL ESTABLISHMENT SHALL HAVE
 IN AN ACCESSIBLE LOCATION AT EACH ENTRY ACCESSIBLE TO
 PEDESTRIANS AT LEAST ONE OUTLET FOR SIGNAGE.
 4. NEC 210.62, THERE SHALL BE A SHOW WINDOW OUTLET FOR
 EVERY 12 FT. OF SHOW WINDOW OR MAJOR PORTION THEREOF OF
 SHOW WINDOW MEASURED HORIZONTALLY. THIS MAY NOT APPLY
 TO EVERY SPACE AS ALL MAY NOT HAVE SHOW WINDOWS.
 5. NEC 300.21, OPENINGS INTO OR THROUGH FIRE RATED
 WALLS, PARTITIONS, FLOORS OR CEILINGS SHALL BE
 FIRESTOPPED USING APPROVED METHODS TO MAINTAIN FIRE
 RESISTANCE RATING.
 6. ALL ENLARGED AREA WILL BE REVIEWED AND COMMENTED
 UPON AT THEIR RESPECTIVE PAGES/VIEWS.
 PG. E301; E302; E303; E304
 1. NEC 700.12, THE LIGHTING CIRCUIT FEEDING EMERGENCY
 AND EXIT LIGHTS SHALL BE THE CIRCUIT AS FOR THE AREA
 THEY OCCUPY UNLESS THERE ARE THREE OR MORE LIGHTING
 CIRCUITS FOR THAT AREA.
 2. SEE NOTES 3 & 4 ABOVE WITH REGARDS TO SIGN AND SHOW
 WINDOW OUTLETS.
 3. LAYERS DO NOT APPEAR TO BE PROPERLY ALIGNED NOR ARE
 WALLS CLEARLY IDENTIFIED TO ASCERTAIN EXIT LIGHT
 REQUIREMENTS.
 4. FBC-E C402.4.8, ALL RECESSED LUMINAIRES INSTALLED IN
 THE BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND
 UNCONDITIONED AIR SPACES.
 PG. E402
 1. NEC 210.8(B)(2), THIRD LEVEL PREP KITCHEN AREA 340,
 ALL 15 VOLT, 15 ? 20 AMP SINGLE PHASE OUTLETS IN
 KITCHENS SHALL HAVE GFCI PROTECTION FOR PERSONNEL.
 2. NEC 210.8 (B)(5), SECOND LEVEL BREAKROOM 231,
 RECEPTACLES INSTALLED WITHIN 6 FT OF THE OUTSIDE EDGE
 OF A SINK SHALL HAVE GFCI PROTECTION FOR PERSONNEL.
 PG. E702
 1. FBC-E C402.4.8, ALL RECESSED LUMINAIRES INSTALLED IN
 THE BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND
 UNCONDITIONED AIR SPACES.
 PG. E1101, E1102
 1. NEC 760.41(B) FIRE ALARM CIRCUITS DISCONNECTING
 MEANS SHALL HAVE A RED IDENTIFICATION, SHALL BE
 ACCESSIBLE ONLY TO QUALIFIED PERSONNEL AND SHALL BE
 IDENTIFIED AS ?FIRE ALARM CIRCUIT.?
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,