| 2015-11-23 18:42:58 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | PG. E050 |
| | 1. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH ELECTRICAL |
| | INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN FOR |
| | INSPECTIONS. NO SITE TUBES WILL BE ACCEPTED. |
| | 2. ALL SITE LIGHTING SHALL BE UNDER SEPARATE PERMIT. |
| | PG. E201; E202; E203; E204 |
| | 1. NEC 314.27(B), BOXES SPECIFICALLY LISTED FOR THE |
| | APPLICATION SHALL BE USED FOR ALL FLOOR OUTLETS. |
| | 2. NEC 406.9(B), ALL 15 & 20 AMP 125 AND 250 VOLT |
| | NONLOCKING RECEPTACLES INSTALLED IN WET LOCATIONS SHALL |
| | BE LISTED WEATHER RESISTANT. |
| | 3. NEC 600.5, EVERY COMMERCIAL ESTABLISHMENT SHALL HAVE |
| | IN AN ACCESSIBLE LOCATION AT EACH ENTRY ACCESSIBLE TO |
| | PEDESTRIANS AT LEAST ONE OUTLET FOR SIGNAGE. |
| | 4. NEC 210.62, THERE SHALL BE A SHOW WINDOW OUTLET FOR |
| | EVERY 12 FT. OF SHOW WINDOW OR MAJOR PORTION THEREOF OF |
| | SHOW WINDOW MEASURED HORIZONTALLY. THIS MAY NOT APPLY |
| | TO EVERY SPACE AS ALL MAY NOT HAVE SHOW WINDOWS. |
| | 5. NEC 300.21, OPENINGS INTO OR THROUGH FIRE RATED |
| | WALLS, PARTITIONS, FLOORS OR CEILINGS SHALL BE |
| | FIRESTOPPED USING APPROVED METHODS TO MAINTAIN FIRE |
| | RESISTANCE RATING. |
| | 6. ALL ENLARGED AREA WILL BE REVIEWED AND COMMENTED |
| | UPON AT THEIR RESPECTIVE PAGES/VIEWS. |
| | PG. E301; E302; E303; E304 |
| | 1. NEC 700.12, THE LIGHTING CIRCUIT FEEDING EMERGENCY |
| | AND EXIT LIGHTS SHALL BE THE CIRCUIT AS FOR THE AREA |
| | THEY OCCUPY UNLESS THERE ARE THREE OR MORE LIGHTING |
| | CIRCUITS FOR THAT AREA. |
| | 2. SEE NOTES 3 & 4 ABOVE WITH REGARDS TO SIGN AND SHOW |
| | WINDOW OUTLETS. |
| | 3. LAYERS DO NOT APPEAR TO BE PROPERLY ALIGNED NOR ARE |
| | WALLS CLEARLY IDENTIFIED TO ASCERTAIN EXIT LIGHT |
| | REQUIREMENTS. |
| | 4. FBC-E C402.4.8, ALL RECESSED LUMINAIRES INSTALLED IN |
| | THE BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND |
| | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND |
| | UNCONDITIONED AIR SPACES. |
| | PG. E402 |
| | 1. NEC 210.8(B)(2), THIRD LEVEL PREP KITCHEN AREA 340, |
| | ALL 15 VOLT, 15 ? 20 AMP SINGLE PHASE OUTLETS IN |
| | KITCHENS SHALL HAVE GFCI PROTECTION FOR PERSONNEL. |
| | 2. NEC 210.8 (B)(5), SECOND LEVEL BREAKROOM 231, |
| | RECEPTACLES INSTALLED WITHIN 6 FT OF THE OUTSIDE EDGE |
| | OF A SINK SHALL HAVE GFCI PROTECTION FOR PERSONNEL. |
| | PG. E702 |
| | 1. FBC-E C402.4.8, ALL RECESSED LUMINAIRES INSTALLED IN |
| | THE BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND |
| | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND |
| | UNCONDITIONED AIR SPACES. |
| | PG. E1101, E1102 |
| | 1. NEC 760.41(B) FIRE ALARM CIRCUITS DISCONNECTING |
| | MEANS SHALL HAVE A RED IDENTIFICATION, SHALL BE |
| | ACCESSIBLE ONLY TO QUALIFIED PERSONNEL AND SHALL BE |
| | IDENTIFIED AS ?FIRE ALARM CIRCUIT.? |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |