Plan Review Notes
Plan Review Notes For Permit 15091225
Permit Number 15091225
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-18 17:33:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. **PENDING RESPONSE FROM DBPR**
  
 2. ENERGY CALCS REQUIRED, FBC ENERGY CONSERVATION 103.
  
 3. FBC 501.2, REVISE PLAN TO INDICATE LOCATION OF
 ADDRESS IDENTIFICATION ON THE BUILDING.
  
 4. THIRD FLOOR SQUARE FOOT AREA ON SHEET A003 IS NOT
 CONSISTENT WITH THE SQUARE FOOT AREA ON A020, PLEASE
 RECONCILE FBC 107. VERIFY ALL FLOORS. THIS IS TO BE
 DONE PRIOR TO IMPACT FEE ASSESSMENT.
  
 6. FBC 1007.1, ACCESSIBILITY 207.1, REVISE PLAN TO
 STATE WHICH OPTION IS ELECTED FOR ACCESSIBLE MEANS OF
 EGRESS. MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE IBC 2000 OR SECTION 1007 OF THE IBC
 2003 EDITION. REVISE PLAN TO CLARIFY COMPLIANCE WITH
 EACH REQUIREMENT OF THE OPTION ELECTED.
  
 7. ADVISORY ONLY, WHEN APPLICATION IS SUBMITTED FOR
 PARKING LOT PAVING AND STRIPING, A050 OR RELATED CIVIL
 SHEET, REVISE PLAN TO PROVIDE THE FOLLOWING
 INFORMATION:
 TOTAL NUMBER OF PARKING SPACES
 NUMBER OF ACCESSIBLE SPACES
  
 FBC 2014 ACCESSIBILITY 208.2 (PARKING SPACES), 502
 (PARKING SPACES).
  
 8. PROVIDE THE VALUE OF THE ITEMS WHICH ARE TO BE ON
 SEPARATE PERMIT AS PER CORRESPONDENCE BETWEEN STEVE
 KENNEDY AND WAYNE CHUBB, FBC 109, FBC 107.
  
 AT THIS TIME, IT APPEARS THAT SEPARATE PERMITS WILL BE
 REQUIRED FOR:
  
 RETRACTABLE AWNINGS (UNLESS ALL INFORMATION PROVIDED IN
 RESUBMITTAL, SEE OTHER COMMENT)
 FREESTANDING TRELLIS AND RETRACTABLE AWNING
 PAVING, HARDSCAPE AND STRIPING
 SITE LIGHTING
 FOUNTAINS
 LANDSCAPING
 DUMPSTER ENCLOSURES
 SIGNAGE (STRUCTURAL DETAIL OF SIGN CONSTRUCTION,
 STRUCTURAL DETAIL FOR ATTACHMENT, ELECTRICAL
 INFORMATION NOT INCLUDED IN THE PERMIT SUBMITTAL)
 BICYCLE RACKS
  
 9. ADVISORY ONLY, SITE LIGHTING IS TO BE ON SEPARATE
 PERMIT. WHEN SUBMITTING, PROVIDE ENGINEERING FOR THE
 SITE LIGHTING AND SITE LIGHTING FIXTURES, FBC 107. THIS
 INFORMATION WAS NOT INCLUDED IN THE SUBMITTAL PACKAGE.
  
 10. FBC 2014 ACCESSIBILITY 404.2.4.1, SHOW MANEUVERING
 CLEARANCE, PULL SIDE (18IN MIN) FOR THE FOLLOWING
 DOORS:
 LEVEL 1 WOMENS AND MENS WC, SHEET A120, A101
 LEVEL 3 DOORS 340.1, 340.2
  
 10. SHEET A120 SPECS AMERICAN STANDARD CADET 3. FBC
 2014 ACCESSIBILITY 604.4, SEAT HEIGHT TO BE 17 IN
 MINIMUM AND 19 IN MAXIMUM. IT IS NOT CLEAR WHICH CADET
 3 MODEL IS PROPOSED, BUT SEAT HEIGHTS ON THE
 MANUFACTURER WEBSITE WERE15IN AND 16.5 IN (TWO
 DIFFERENT MODELS CHECKED). REVISE PLAN TO SHOW SEAT
 HEIGHT OR SEAT HEIGHT RANGE AND CLARIFY CADET 3 MODEL
 PROPOSED (OR REMOVE MODEL SPEC).
  
 11. SHEET A120, SPECIFY DRINKING FOUNTAIN HEIGHTS OR
 HEIGHT RANGES, FBC 2014 ACCESSIBILITY 602.4, 602.7.
  
 12. PLANS SHOW THE RETRACTABLE AWNING AS "BY OWNER." IF
 AWNINGS ARE TO BE INCLUDED IN THIS PERMIT, PROVIDE
 STRUCTURAL DETAILS FOR THE RETRACTABLE AWNINGS, FBC
 107, INCLUDING WIND DESIGN CRITERIA FBC 1609, FASTENING
 INFORMATION, FABRIC INFORMATION TO SHOW COMPLIANCE WITH
 FBC 3105. IF ALL REQUIRED INFORMATION IS NOT PROVIDED,
 A SEPARATE PERMIT FOR THE AWNINGS WILL BE REQUIRED. IT
 IS NOT CLEAR WHETHER THIS IS TO MEET THE SAME WIND
 REQUIREMENTS OF THE BUILDING, OR IF IT IS A RISK
 CATEGORY 1, OR DESIGNED USING FBC3105.4.
  
 13. DUE TO PARKING CONFIGURATION, IT APPEARS THAT VALET
 PARKING WILL BE AVAILABLE. SEE FBC 503.3.2 AND .3;
 PLEASE REVISE PLAN TO INDICATE PULL UP SPACE AND ACCESS
 AISLE MARKING.
  
 14. PROVIDE STRUCTURAL DETAILS FOR THE STATIONARY
 AWNINGS, FBC 107, INCLUDING WIND DESIGN CRITERIA FBC
 1609, IF THEY ARE TO BE INCLUDED IN THIS PERMIT RATHER
 THAN BEING INCLUDED ON A SEPARATE PERMIT.
  
 15. A428 AND OTHER LOCATIONS, PLYWOOD SHEATHING SHOWN;
 REVISE TO SPECIFY FRT OR INCLUDE APPLICABLE EXCEPTION
 FBC TABLE 602.
  
 16. S421, REVISE PLAN TO INCLUDE PAGE NUMBER FOR THE
 "CMU REINF SCHED" REFERRED TO IN DETAIL 19, FBC 107.
  
 17. S421, VERTICAL STEEL REQUIRED IS NOT CLEAR, DETAIL
 20. TWO ARROWS ARE SHOWN BUT NOT SPECIFIED, TEXT STATES
 "#4 @ 16IN", DOES THIS MEAN TWO #4 AT 16IN OC? FBC 107.
  
 18. S002, RCSC REFERENCE NOT CONSISTENT WITH THE FBC
 2014. REVISE AND CHECK ALL STANDARDS; SEE FBC CHAPTER
 35. IF DESIGNER WOULD LIKE TO PROPOSE AN ALTERNATE,
 THIS MUST BE REQUESTED USING ALTERNATIVE MATERIALS AND
 METHODS FBC 104.11. CONTACT ME VIA EMAIL FOR FURTHER
 INFORMATION IF THIS IS DESIGNER'S INTENT.
  
 19. PROVISO: ADVISORY ONLY, PRODUCT APPROVALS FOR ALL
 COMPONENTS AND CLADDING ARE TO BE SUBMITTED PRIOR TO
 INSTALLATION, REVIEWED BY DOR PRIOR TO SUBMITTAL.
 COMPONENTS AND CLADDING TO COMPLY WITH THE PRESSURE ON
 PAGE S102.
  
  
  