| 2015-11-18 17:33:23 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. **PENDING RESPONSE FROM DBPR** |
| | |
| | 2. ENERGY CALCS REQUIRED, FBC ENERGY CONSERVATION 103. |
| | |
| | 3. FBC 501.2, REVISE PLAN TO INDICATE LOCATION OF |
| | ADDRESS IDENTIFICATION ON THE BUILDING. |
| | |
| | 4. THIRD FLOOR SQUARE FOOT AREA ON SHEET A003 IS NOT |
| | CONSISTENT WITH THE SQUARE FOOT AREA ON A020, PLEASE |
| | RECONCILE FBC 107. VERIFY ALL FLOORS. THIS IS TO BE |
| | DONE PRIOR TO IMPACT FEE ASSESSMENT. |
| | |
| | 6. FBC 1007.1, ACCESSIBILITY 207.1, REVISE PLAN TO |
| | STATE WHICH OPTION IS ELECTED FOR ACCESSIBLE MEANS OF |
| | EGRESS. MEANS OF EGRESS SHALL COMPLY WITH SECTION |
| | 1003.2.13 OF THE IBC 2000 OR SECTION 1007 OF THE IBC |
| | 2003 EDITION. REVISE PLAN TO CLARIFY COMPLIANCE WITH |
| | EACH REQUIREMENT OF THE OPTION ELECTED. |
| | |
| | 7. ADVISORY ONLY, WHEN APPLICATION IS SUBMITTED FOR |
| | PARKING LOT PAVING AND STRIPING, A050 OR RELATED CIVIL |
| | SHEET, REVISE PLAN TO PROVIDE THE FOLLOWING |
| | INFORMATION: |
| | TOTAL NUMBER OF PARKING SPACES |
| | NUMBER OF ACCESSIBLE SPACES |
| | |
| | FBC 2014 ACCESSIBILITY 208.2 (PARKING SPACES), 502 |
| | (PARKING SPACES). |
| | |
| | 8. PROVIDE THE VALUE OF THE ITEMS WHICH ARE TO BE ON |
| | SEPARATE PERMIT AS PER CORRESPONDENCE BETWEEN STEVE |
| | KENNEDY AND WAYNE CHUBB, FBC 109, FBC 107. |
| | |
| | AT THIS TIME, IT APPEARS THAT SEPARATE PERMITS WILL BE |
| | REQUIRED FOR: |
| | |
| | RETRACTABLE AWNINGS (UNLESS ALL INFORMATION PROVIDED IN |
| | RESUBMITTAL, SEE OTHER COMMENT) |
| | FREESTANDING TRELLIS AND RETRACTABLE AWNING |
| | PAVING, HARDSCAPE AND STRIPING |
| | SITE LIGHTING |
| | FOUNTAINS |
| | LANDSCAPING |
| | DUMPSTER ENCLOSURES |
| | SIGNAGE (STRUCTURAL DETAIL OF SIGN CONSTRUCTION, |
| | STRUCTURAL DETAIL FOR ATTACHMENT, ELECTRICAL |
| | INFORMATION NOT INCLUDED IN THE PERMIT SUBMITTAL) |
| | BICYCLE RACKS |
| | |
| | 9. ADVISORY ONLY, SITE LIGHTING IS TO BE ON SEPARATE |
| | PERMIT. WHEN SUBMITTING, PROVIDE ENGINEERING FOR THE |
| | SITE LIGHTING AND SITE LIGHTING FIXTURES, FBC 107. THIS |
| | INFORMATION WAS NOT INCLUDED IN THE SUBMITTAL PACKAGE. |
| | |
| | 10. FBC 2014 ACCESSIBILITY 404.2.4.1, SHOW MANEUVERING |
| | CLEARANCE, PULL SIDE (18IN MIN) FOR THE FOLLOWING |
| | DOORS: |
| | LEVEL 1 WOMENS AND MENS WC, SHEET A120, A101 |
| | LEVEL 3 DOORS 340.1, 340.2 |
| | |
| | 10. SHEET A120 SPECS AMERICAN STANDARD CADET 3. FBC |
| | 2014 ACCESSIBILITY 604.4, SEAT HEIGHT TO BE 17 IN |
| | MINIMUM AND 19 IN MAXIMUM. IT IS NOT CLEAR WHICH CADET |
| | 3 MODEL IS PROPOSED, BUT SEAT HEIGHTS ON THE |
| | MANUFACTURER WEBSITE WERE15IN AND 16.5 IN (TWO |
| | DIFFERENT MODELS CHECKED). REVISE PLAN TO SHOW SEAT |
| | HEIGHT OR SEAT HEIGHT RANGE AND CLARIFY CADET 3 MODEL |
| | PROPOSED (OR REMOVE MODEL SPEC). |
| | |
| | 11. SHEET A120, SPECIFY DRINKING FOUNTAIN HEIGHTS OR |
| | HEIGHT RANGES, FBC 2014 ACCESSIBILITY 602.4, 602.7. |
| | |
| | 12. PLANS SHOW THE RETRACTABLE AWNING AS "BY OWNER." IF |
| | AWNINGS ARE TO BE INCLUDED IN THIS PERMIT, PROVIDE |
| | STRUCTURAL DETAILS FOR THE RETRACTABLE AWNINGS, FBC |
| | 107, INCLUDING WIND DESIGN CRITERIA FBC 1609, FASTENING |
| | INFORMATION, FABRIC INFORMATION TO SHOW COMPLIANCE WITH |
| | FBC 3105. IF ALL REQUIRED INFORMATION IS NOT PROVIDED, |
| | A SEPARATE PERMIT FOR THE AWNINGS WILL BE REQUIRED. IT |
| | IS NOT CLEAR WHETHER THIS IS TO MEET THE SAME WIND |
| | REQUIREMENTS OF THE BUILDING, OR IF IT IS A RISK |
| | CATEGORY 1, OR DESIGNED USING FBC3105.4. |
| | |
| | 13. DUE TO PARKING CONFIGURATION, IT APPEARS THAT VALET |
| | PARKING WILL BE AVAILABLE. SEE FBC 503.3.2 AND .3; |
| | PLEASE REVISE PLAN TO INDICATE PULL UP SPACE AND ACCESS |
| | AISLE MARKING. |
| | |
| | 14. PROVIDE STRUCTURAL DETAILS FOR THE STATIONARY |
| | AWNINGS, FBC 107, INCLUDING WIND DESIGN CRITERIA FBC |
| | 1609, IF THEY ARE TO BE INCLUDED IN THIS PERMIT RATHER |
| | THAN BEING INCLUDED ON A SEPARATE PERMIT. |
| | |
| | 15. A428 AND OTHER LOCATIONS, PLYWOOD SHEATHING SHOWN; |
| | REVISE TO SPECIFY FRT OR INCLUDE APPLICABLE EXCEPTION |
| | FBC TABLE 602. |
| | |
| | 16. S421, REVISE PLAN TO INCLUDE PAGE NUMBER FOR THE |
| | "CMU REINF SCHED" REFERRED TO IN DETAIL 19, FBC 107. |
| | |
| | 17. S421, VERTICAL STEEL REQUIRED IS NOT CLEAR, DETAIL |
| | 20. TWO ARROWS ARE SHOWN BUT NOT SPECIFIED, TEXT STATES |
| | "#4 @ 16IN", DOES THIS MEAN TWO #4 AT 16IN OC? FBC 107. |
| | |
| | 18. S002, RCSC REFERENCE NOT CONSISTENT WITH THE FBC |
| | 2014. REVISE AND CHECK ALL STANDARDS; SEE FBC CHAPTER |
| | 35. IF DESIGNER WOULD LIKE TO PROPOSE AN ALTERNATE, |
| | THIS MUST BE REQUESTED USING ALTERNATIVE MATERIALS AND |
| | METHODS FBC 104.11. CONTACT ME VIA EMAIL FOR FURTHER |
| | INFORMATION IF THIS IS DESIGNER'S INTENT. |
| | |
| | 19. PROVISO: ADVISORY ONLY, PRODUCT APPROVALS FOR ALL |
| | COMPONENTS AND CLADDING ARE TO BE SUBMITTED PRIOR TO |
| | INSTALLATION, REVIEWED BY DOR PRIOR TO SUBMITTAL. |
| | COMPONENTS AND CLADDING TO COMPLY WITH THE PRESSURE ON |
| | PAGE S102. |
| | |
| | |
| | |