2015-12-03 09:33:541ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
  
  
 (A) GENERAL PROVISIONS. IN EVERY KITCHEN, FAMILY ROOM,
 DINING ROOM, LIVING ROOM, PARLOR, LIBRARY, DEN,
 SUNROOM,
 BEDROOM, RECREATION ROOM, OR SIMILAR ROOM OR AREA OF
 DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED
 IN ACCORDANCE
 WITH THE GENERAL PROVISIONS SPECIFIED IN 210.52(A)(1)
 THROUGH (A)(3).
  
 (3) BALCONIES, DECKS, AND PORCHES. BALCONIES, DECKS,
 AND
 PORCHES THAT ARE ACCESSIBLE FROM INSIDE THE DWELLING
 UNIT
 SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET INSTALLED
 WITHIN THE
 PERIMETER OF THE BALCONY, DECK, OR PORCH. THE
 RECEPTACLE
 SHALL NOT BE LOCATED MORE THAN 2.0 M (61?2 FT) ABOVE
 THE
 BALCONY, DECK, OR PORCH SURFACE.
  
 210.70 LIGHTING OUTLETS REQUIRED. LIGHTING OUTLETS
 SHALL
 BE INSTALLED WHERE SPECIFIED IN 210.70(A), (B), AND
 (C).
 (A) DWELLING UNITS. IN DWELLING UNITS, LIGHTING OUTLETS
 SHALL BE INSTALLED IN ACCORDANCE WITH 210.70(A)(1),
 (A)(2),
 AND (A)(3).
 (1) HABITABLE ROOMS. AT LEAST ONE WALL
 SWITCH?CONTROLLED
 LIGHTING OUTLET SHALL BE INSTALLED IN EVERY HABITABLE
 ROOM
 AND BATHROOM.
  
 (B) FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL SWITCH?
 CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO
 PROVIDE ILLUMINATION
 ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS
 WITH GRADE LEVEL ACCESS.