| 2015-12-16 07:34:46 | 2ND REVIEW 2010 MECHANICAL | | | PERMIT REVISION #15091217 | | | 12/16/15 | | | | | | 1) IN RESPONSE TO THE MOST RECENT LETTER FROM TRANE | | | DATED NOVEMBER 5, 2015, PLEASE SEE SECTION 301.4 FBC-10 | | | MECHANICAL: 301.7 LISTED AND LABELED. | | | APPLIANCES REGULATED BY THIS CODE SHALL BE LISTED AND | | | LABELED FOR THE APPLICATION IN WHICH THEY ARE INSTALLED | | | AND USED, UNLESS OTHERWISE APPROVED IN ACCORDANCE WITH | | | SECTION 301.4.1. | | | EXCEPTION: LISTING AND LABELING OF EQUIPMENT AND | | | APPLIANCES USED FOR REFRIGERATION SHALL BE IN | | | ACCORDANCE WITH SECTION 1101.2. | | | ALTHOUGH THE LETTER STATES "DISCONNECTING AND REMOVING | | | THE HEATERS .....IS ACCEPTABLE TO TRANE", THE LETTER | | | ALSO STATES THE "FACTORY NAMEPLATE WILL NOT REFLECT | | | THIS CHANGE". DUE TO THE FACT THAT THE PRODUCT WAS | | | TESTED, APPROVED, AND LISTED WITH THE HEATERS IN TACT | | | AS PART OF THE PRODUCT ASSEMBLY, THE NAMEPLATE OR LABEL | | | IS NO LONGER VALID SINCE THE HEATERS HAVE BEEN REMOVED | | | IN THE FIELD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|