Plan Review Notes
Plan Review Notes For Permit 15091217
Permit Number 15091217
Review Stop M
Sequence Number 2
Notes
Date Text
2015-12-16 07:34:462ND REVIEW 2010 MECHANICAL
 PERMIT REVISION #15091217
 12/16/15
  
 1) IN RESPONSE TO THE MOST RECENT LETTER FROM TRANE
 DATED NOVEMBER 5, 2015, PLEASE SEE SECTION 301.4 FBC-10
 MECHANICAL: 301.7 LISTED AND LABELED.
 APPLIANCES REGULATED BY THIS CODE SHALL BE LISTED AND
 LABELED FOR THE APPLICATION IN WHICH THEY ARE INSTALLED
 AND USED, UNLESS OTHERWISE APPROVED IN ACCORDANCE WITH
 SECTION 301.4.1.
 EXCEPTION: LISTING AND LABELING OF EQUIPMENT AND
 APPLIANCES USED FOR REFRIGERATION SHALL BE IN
 ACCORDANCE WITH SECTION 1101.2.
 ALTHOUGH THE LETTER STATES "DISCONNECTING AND REMOVING
 THE HEATERS .....IS ACCEPTABLE TO TRANE", THE LETTER
 ALSO STATES THE "FACTORY NAMEPLATE WILL NOT REFLECT
 THIS CHANGE". DUE TO THE FACT THAT THE PRODUCT WAS
 TESTED, APPROVED, AND LISTED WITH THE HEATERS IN TACT
 AS PART OF THE PRODUCT ASSEMBLY, THE NAMEPLATE OR LABEL
 IS NO LONGER VALID SINCE THE HEATERS HAVE BEEN REMOVED
 IN THE FIELD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  