2015-10-06 08:40:531ST REVIEW: FBC 2010 MECHANICAL
 REVISION #15091217, MASTER #15050778
 10/6/15
  
 1) THE LETTER FROM MR. NERI OF TRANE SOUTH FLORIDA
 ASSOCIATED WITH THIS PLAN REVISION WAS SUBMITTED
 WITHOUT SIGNATURE. IN ADDITION, THE LETTER IS
 REQUESTING THAT AN INSPECTOR APPROVE MECHANICAL
 EQUIPMENT (VAV BOXES) THAT WILL BE ALTERED IN THE FIELD
 WITHOUT CERTIFICATION BY THE MANUFACTURER OR THE
 LISTING AND LABELING AGENCY- SECTION 301.4 FBC-10
 MECHANICAL.
 2) PLEASE NOTE THAT INSTALLATION OF THE NEW DUCT
 HEATERS WILL REQUIRE A REVISION TO THE APPROVED
 ELECTRICAL PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER